User Manual Owner's manual
Publication 1757-UM006A-EN-P - May 2002
2-18 Integrating Fieldbus into Rockwell Automation Logix System
The status byte structure consists of a 2-bit quality, most significant bit,
field; a 4-bit substatus field; and a 2-bit limits, least significant bit,
field. The following table provides a breakdown of bit assignments for
general reference. The value of the quality field determines the
applicable substatus field indication.
Fieldbus Status Indications
See Appendix B for list of possible display indications associated with
a given fieldbus status.
Table 2.B Breakdoun of bit assignments
Bit Quality Substatus, if Quality field is Limits
BAD UNCERTAIN GOOD
(Non-Cascade)
(1)
GOOD (Cascade)
(1)
0 BAD Data Quality Non-Specific Non-Specific Non-Specific Non-Specific No Limits
1UNCERTAIN Data
Quality
Configuration Error Last Usable Value Active Block Alarm Initialization
Acknow-ledge (IA)
Low Limit
2 GOOD
(Non-Cascade)
Data Quality
Not Connected Substitute Active Advisory
Alarm
Initialization Request
(IR)
High Limit
3 GOOD (Cascade)
Data Quality
Device Failure Initial Value Active Critical
Alarm
Not Invited (NI) Constant
4 Sensor Failure Sensor Conversion
Not Accurate
Unacknow-ledged
Block Alarm
Not Selected (NS)
5 No Communication, with
Last Usable Value
Engineering Unit
Range Violation
Unacknow-ledged
Advisory Alarm
Do Not Select (DNS)
6 No Communication, with
no Last Usable Value
Sub-Normal Unacknow-leged
Critical Alarm
Local Override (LO)
7 Out-Of-Service Fault-State Active (FSA)
8 Initiate Fault-State (IFS)
(1)
The Good (non-cascade) substatus is used by output connections for fieldbus blocks such as Analog Input and Discrete Input. The Good (cascade) substatus is used by
output connections for fieldbus blocks such as PID. Both of these substatuses are converted to the single ProcessLogix data quality of Good.