User Manual Owner's manual
Publication 1757-UM006A-EN-P May 2002
1788-CN2FF Installation Example F-53
The Transducer FB window opens.
If the OOS is active:
Table F.3
If: Then:
the OOS is active • Click on the “Auto” button, to put
the Transducer Block in “Auto”
mode.
the Transducer goes into Auto mode, and if
that was your only problem
• The bad data indication will go
away.
the Transducer FB doesn’t go into Auto • Check the mode of the Resource
Block and the AI Block.
• All should be in Auto Mode.
• If the Transducer will not go into
Auto Mode refer to the FF device
manufacturer for help.
• You also need to have the RB
Resource Block in Auto Mode.