User Manual Owner's manual

Publication 1757-UM006A-EN-P May 2002
1788-CN2FF Installation Example F-53
The Transducer FB window opens.
If the OOS is active:
Table F.3
If: Then:
the OOS is active Click on the Auto button, to put
the Transducer Block in Auto
mode.
the Transducer goes into Auto mode, and if
that was your only problem
The bad data indication will go
away.
the Transducer FB doesnt go into Auto Check the mode of the Resource
Block and the AI Block.
All should be in Auto Mode.
If the Transducer will not go into
Auto Mode refer to the FF device
manufacturer for help.
You also need to have the RB
Resource Block in Auto Mode.