User Manual Owner's manual

Publication 1757-UM006A-EN-P May 2002
F-2 1788-CN2FF Installation Example
Required Hardware for
Installation Example
One 1788-CN2FF, ControlNet to Fieldbus Linking Device
One 24 Power Supply for the CN2FF, such as 1794-PS1
1794-PS1 is a good power supply for use with the CN2FF, and
is OK to use for a small demo with one or two Fieldbus
devices, but it is too noisy for a real control application.
FF convenience Relcom Connector Blocks.
Connector block should include built in power conditioner
and two Fieldbus terminators.
One Personal Computer, 233 MHz or faster, 128 Meg Memory
With Windows NT, Service Pack 3 or later.
You must use Windows NT/2000. The 1788-FFCT software is not
compatible with Windows 95/98.
High Resolution Monitor, 1200 x 1024 recommended.
Use at least 1024 x 800. The Fieldbus Configurator is much
easier to use with a high resolution monitor. If you use a 640 X
480 screen, you will be unable to find some of the items on
the toolbars.
1784-PCIC, 1784-KTCX15 or 1784-PCC card, for direct
connection to ControlNet.
PLC-5, or CLX, or PLX, or SLC with a ControlNet Interface.
One Operating ControlNet Network supporting the Controller,
the PLC-5, CLX or PLX, or SLC, plus a PC with KTCX15,
1784-PCC or a 1784-PCIC and one or more 1788-CN2FFs
One or more Registered Fieldbus devices.
1788-FFCT software requires that the Fieldbus devices be
on-line. Off-line configuration will be supported later.