User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
A-38 Standard Function Block Parameters
Table A.102 ROUT_OUT
Table A.103 RS_STATE
Valid Views
VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
Status
Value
Classification
Record
Description
Represents block output and status. It serves as input to a host for back calcu-
lation in ROut mode that allows action to be taken under limited conditions or
mode change
FF Data Type
DS-65
Usage
C/Remote-Output Out
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
Read Only
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
Status
Value
Classification
Simple Variable
Description
Defines the state of the function block application state machine.
FF Data Type
Unsigned 8
Range
1: Start/Restart
2: Initialization
3: On-Line Linking
4: On-Line
5: Standby
6: Failure
Usage
C/Resource State
Length
1
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only