User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-35
Table A.94 RCAS_IN_D
Table A.95 RCAS_OUT
Table A.96 RCAS_OUT_D
Classification
Record
Description
Represents target setpoint and status provided by a supervisory host to the
analog control or output block.
FF Data Type
DS-66
Usage
C/Remote-Cascade In
Length
2
Valid Views
VIEW_3
Storage
Non-Volatile
Remarks
The data type consists of the value and status of discrete value parameters. It
uses the following two elements.
Status
Value
Classification
Record
Description
Represents block setpoint and status after ramping. It serves as input to a
supervisory host for back calculation that allows action to be taken under lim-
iting conditions or mode change.
FF Data Type
DS-65
Usage
C/Remote-Cascade Out
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
Read Only
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
Status
Value
Classification
Record
Description
Represents block setpoint and status. It serves as input to a supervisory host
for back calculation that allows action to be taken under limiting conditions or
mode change.
FF Data Type
DS-66
Usage
C/Remote-Cascade Out
Length
2