User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-29
Nxxx Blocks
Table A.79 NV_CYCLE_T
Oxxx Blocks
Table A.80 OUT
Valid Views
VIEW_1, VIEW_3
Storage
mix
Remarks
Normally, the operator has permission to write these values, but PROGRAM or
LOCAL remove that permission and grant it to a supervisory computer or a
local control panel.
This block has a mixture of storage types. Static for modes Normal and Permit-
ted, Non-Volatile for Target mode, and Dynamic for Actual mode.
The data type consists of bit strings for Actual, Target Permitted and Normal
modes. It uses the following four elements.
Target
Actual
Permitted
Normal
Classification
Simple Variable
Description
Defines interval between writing copies of Non-Volatile (NV) parameters to
NV memory. Zero means never.
FF Data Type
Unsigned 32
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
Ready Only
Classification
Record
Description
Represents the primary analog value calculated as a result of executing the
function.
FF Data Type
DS-65
Range
OUT_SCALE +/- 10 percent
Usage
O/Primary Output
Length
5