User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-21
Table A.57 HI_HI_LIM
Table A.58 HI_HI_PRI
Table A.59 HI_LIM
Length
16
Storage
Dynamic
Remarks
Read Only
The Data type consists of data that describes floating point alarms. It uses the
following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value
Classification
Simple Variable
Description
Defines the high high alarm limit setting in engineering units.
FF Data Type
Float
Range
PV_SCALE, + infinity
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is + infinity
Classification
Simple Variable
Description
Defines priority of the high high alarm.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0
Classification
Simple Variable
Description
Defines the high alarm limit setting in engineering units.
FF Data Type
Float
Range
PV_SCALE, + infinity