User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
A-20 Standard Function Block Parameters
Hxxx Blocks
Table A.54 HARD_TYPES
Table A.55 HI_ALM
Table A.56 HI_HI_ALM
Classification
Simple Variable
Description
Identifies types of hardware that are available as channel numbers on this
resource.
FF Data Type
Bit String
Range
Set by manufacturer
Usage
C/Contained
Length
2
Valid Views
VIEW_4
Storage
Static
Remarks
Read Only
Classification
Record
Description
Identifies the status and time stamp associated with the high alarm.
FF Data Type
DS-71
Usage
C/Alarm
Length
16
Storage
Dynamic
Remarks
Read Only
The Data type consists of data that describes floating point alarms. It uses the
following five elements.
Unacknowledged
Alarm State
Time Stamp
Subcode
Value
Classification
Record
Description
Identifies the status and time stamp associated with the high high alarm.
FF Data Type
DS-71
Usage
C/Alarm