User Manual Owner's manual

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-9
Table A.23
CONTROL_OPTS Bit Selections
Table A.24 CYCLE_SEL
Valid Views
VIEW_4
Storage
Static
Remarks
See the following for a list of the control options by bit and applicable function
block.
Bit Meaning Function Block
BG CS ML PD PID RA
0 Bypass Enable (LSB) X X
1 SP-PV Track in Man X X X
2 SP-PV Track in ROut X X
3 SP-PV Track in LO or IMan X X X
4 SP Track retained target X X X X
5 Direct Acting X X
6 Balance Ramp X X X
7 Track Enable X X X X X
8 Track in Manual X X X X X
9 Use PV for BKCAL_OUT X X X
10 Act on IR X X X
11 Use percent for IN_1 X X
12 Obey SP limits if Cas or RCas X X X X
13No OUT limits in Manual XXXXXX
14 Reserved
15 Reserved
Classification
Simple Variable
Description
A bit string to identify the block execution method selected for this resource.
FF Data Type
Bit String
Usage
C/Contained
Length
2
Valid Views
VIEW_2
Storage
Static
Remarks
Changing this parameter may be fatal to communication.