Standard Function Block Parameters A-7
Cxxx Blocks
Table A.17 CAS_IN
Table A.18 CAS_IN_D
Table A.19 CHANNEL
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 0.
Classification
Record
Description
Represents the remote setpoint value that must come from another fieldbus
block or a distributed control system (DCS) block through a defined link.
FF Data Type
DS-65
Usage
I/Cascade Input
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
Status
Value
Classification
Record
Description
Represents the remote setpoint value for a discrete block that must come from
another fieldbus block or a distributed control system (DCS) block through a
defined link.
FF Data Type
DS-66
Usage
I/Cascade Input
Length
2
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of discrete value parameters. It
uses the following two elements.
Status
Value
Classification
Simple Variable
Description
The number of the logical hardware channel that is connected to this I/O
block. It defines the transducer used to connect to the physical world.
FF Data Type
Unsigned 16
Range
1 to Manufacturer Limit