User Manual Owner's manual
Publication 1757-UM006A-EN-P - May 2002
4-42 Configurating the 1757-FIM
6. Click the Alarms tab.
7. Enter or select the following values for these Alarm Limits:
Leave all other Alarm Limits at their default values.
8. Click the Block Pins tab.
Alarm Limit Trip Point Priority Severity
PV High High 85 URGENT 15
PV High 70 HIGH 8
PV Low 25 HIGH 8
PV Low Low 15 URGENT 15