User manual

Publication 1760-UM001A-EN-P
2-8 Installation
Connecting AC Inputs
Connect inputs to push-buttons, switches, relays, or contacts.
Wire Lengths
Severe electromagnetic interference to wires can cause inputs to signal 1 without
the proper signal being applied. Observe the following maximum cable lengths:
I1 to I6, I9 to I12: 40m (130 ft) without additional circuits
I7 and I8: 100m (330 ft) without additional circuits
ATTENTION
!
!!
!
For Pico controllers with ac inputs, connect the inputs to the
same phase as the power feed L1, in accordance with VDE, IEC,
UL and CSA safety regulations. Otherwise, Pico may not detect
the switching level or, it may be damaged by excess voltage.
Input Specification
Input Signal Voltage Range OFF signal: 0 to 40V ac
ON signal: 79V to 264V ac
Input Current I1 to I6, I9 to I12: 0.25 mA at 120V ac, 0.5 mA at 240V ac
I7 and I8: 4 mA at 120V ac, 6 mA at 240V ac,
ATTENTION
!
!!
!
Do not use reed relay contacts on I7 or I8. These may burn or
melt due to the high current of I7 and I8.
L1 L2 I2 I3 I4 I5 I6 I7 I8I1
120/240V ac
50/60Hz
Inputs x 120/240V ac
L1
L2
F1