User manual
Publication 1760-UM001A-EN-P
2-2 Installation
by EN 50178, see the appropriate sections in this publication, as well as the
Allen-Bradley publication Industrial Automation Wiring and Grounding
Guidelines For Noise Immunity, publication 1770-4.1.
This equipment is classified as open equipment and must be mounted in an
enclosure during operation to provide safety protection.
Mounting
Install Pico in an enclosure, switch cabinet, or distribution board so that the power
feed and terminal connections cannot be touched accidentally during operation.
Clip Pico onto a DIN rail or install directly onto a panel using the mounting feet.
Pico can be mounted either vertically or horizontally.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 3
cm (1.18 in.) of space on all sides for adequate ventilation, as shown:
DIN Rail Mounting
1. Mount your DIN rail. (Make sure that the
placement of the Pico unit on the DIN rail meets
the recommended spacing requirements.
2. Hook the top slot over the DIN rail.
3. While pressing the Pico unit down against the top
of the rail, snap the bottom of the unit into
position. Ensure DIN latches are in the up
(secured) position.
Pico can be mounted vertically on a DIN rail in the
same way.
1.18"
1.18"
1.18"
1.18"