User manual

Publication 1760-UM001A-EN-P
6-6 Pico System Settings
The following requirements must be fulfilled for a parameter set to be displayed:
a function relay must have been included in the circuit diagram
the parameter set has been enabled for access, indicated by the “+” character at
the bottom right of the display.
Use the PARAMETER menu to access and modify accessible parameter sets.
Parameter sets for which access is not enabled are not displayed. Pico therefore
allows you to protect parameters with the use of a password. You can enable or
disable parameter access using the parameter “+”or “-” characters respectively in the
circuit diagram.
Use up or down arrows to scroll through the parameter
sets. The cursor must be located on the identifier of the
function relay, in this case T1.
Change the values for a parameter set:
left and right arrows move between the parameters
up and down arrows change the value of a parameter
Ok Save parameter or Esc Retain previous setting.
The cursor moves back to the identifier T1.
Press Esc to leave the parameter display. The parameter display is opened via the
PARAMETER menu. “{” coil terminals for counters and timers are not displayed
here, even if they have been programmed.
Variable Parameters for Function Relays
You can modify the relay parameters used in the circuit diagram in three different
ways:
All circuit diagram parameters can be adjusted in Stop mode via the circuit
diagram.
Setpoints can be modified in Run mode via the circuit diagram.
Setpoints can be modified via the PARAMETER menu.
The following setpoints can be modified
the timer setpoints for timing relays
the counter setpoints of counter relays
the day and ON/OFF times of time switches
the comparison setpoint of analog comparators.
In Run mode, Pico operates with a new setpoint as soon has it is modified in the
parameter display and saved.
00.00
30.00
TRG
RES
S
T1
+