User manual
Publication 1760-UM001D-EN-P - September 2005
Specifications A-3
Power Supply
AC Models
Resolution
Range “s” 10 ms
Range “M:S” 1s
Range “H:M” 1 min.
Retentive memory
Write cycles of the
retentive memory
≥100,000
Ambient mechanical conditions
Specification Value Standard
Incoming Power 1760-L12AWA
1760-L12AWA-NC
1760-L12AWA-ND
1760-L18AWA
1760-L18AWA-EX
1760-L18AWA-EXND
1760-IA12XOW6I
1760-L12NWN
1760-L12NWN-ND
1760-L18NWN-EX
1760-L18NWN-EXND
Rated value (sinusoidal) 100 to 240V ac +10/-15% 100 to 240V ac +10/-15% 24V ac, +10/-15 %
Range 90 to 264V ac 85 to 264V ac 20.4 to 26.4V ac
Frequency, rated value, tolerance 50/60 Hz, ±5% 50/60 Hz, ±5% 50/60 Hz, ±5%
Line Current
at 115/120V ac 60 Hz Nominal 40 mA Nominal 70 mA
at 230/240V ac 50 Hz Nominal 20 mA Nominal 35 mA
at 24V ac 50/60 Hz Nominal 200 mA (1760-L12)
Nominal 300 mA ((1760-L18)
Voltage dips 20 ms, EN 61131-2 20 ms, EN 61131-2 20 ms, EN 61131-2
Power Consumption
at 115/120V ac Nominal 5 VA Nominal 10 VA
at 230/240V ac Nominal 5 VA Nominal 10 VA
at 24V ac Nominal 5 VA (1760-L12)
Nominal 7 VA (1760-L18)