Owner manual

Chapter 6
1503E-IN001E-EN-P June 2013
Contactor Installation
Introduction The MV SMC Flex components are designed for intermittent starting
duty. A bypass contactor must be used to bypass the power stacks
once the motor is at full speed.
A line contactor is also required in order to isolate the power stacks
from line voltage. A suitable medium voltage circuit breaker may be
substituted for the line contactor.
Main and Bypass Contactors Refer to Table 6.A for the required installation for contactors.
Table 6.A Required Installation Instructions for OEM Components
Component
Required Installation Documents
Isolation Contactor
User Manual OEM Frame and Components, Bulletin 1503,
Publication 1503-5.0
User Manual Medium Voltage Contactor, Series E, Bulletin 1502,
400 Amp, Publication 1502-UM052_-EN-P or
Series D, Publication 1502-UM050_-EN-P or
Medium Voltage Contactor, Series D & E, Bulletin 1502, 800 Amp,
Publication 1502-UM051_-EN-P
Bypass Contactor
User Manual Medium Voltage Contactor, Series E, Bulletin 1502,
400 Amp, Publication 1502-UM052_-EN-P or
Series D, Publication 1502-UM050_-EN-P or
Medium Voltage Contactor, Series D & E, Bulletin 1502, 800 Amp,
Publication 1502-UM051_-EN-P
Bypass Contactor A bypass contactor must be used in the SMC configuration to bypass
the SCRs once the motor is up to speed.
Refer to User Manual, MV SMC Flex™ Motor Controller, Bulletin
1503E, 1560E, 1562E, Publication 1560E-UM051_-EN-P for more
information on the bypass contactor and the duty cycle. This
publication was included with your shipment.
A T T E N T I O NA T T E N T I O N
A bypass contactor must be installed to complete
the SMC configuration. SCRs are not rated for
continuous duty. The duty cycle is limited to 60
seconds per hour. This can be a combination of
starting and stopping cycles that does not exceed
30 seconds per cycle. Failure to install a bypass
contactor may result in damage to components
from overheating.