3-2 Power Stack Frame Installation
1503E-IN001E-EN-P June 2013
Description of Frame Options
Catalog Number
Part Number
1000V, 180 A, 3 phase, 50/60 Hz
1503E-FRZ1T
80187-547-51
1000V, 360 A, 3 phase, 50/60 Hz
1503E-FRZ1A
80187-547-52
2300V, 180 A, 3 phase, 50/60 Hz
1503E-FRAT
80187-547-53
2300V, 360 A, 3 phase, 50/60 Hz
1503E-FRAA
80187-547-54
3300V, 180 A, 3 phase, 50/60 Hz
1503E-FRCT
80187-547-55
3300V, 360 A, 3 phase, 50/60 Hz
1503E-FRCA
80187-547-56
4160V, 180 A, 3 phase, 50/60 Hz
1503E-FRET
80187-547-57
4160V, 360 A, 3 phase, 50/60 Hz
1503E-FREA
80187-547-58
Voltage ranges : 1000 = 800 to 1449 V
2300 = 1450 to 2499 V
3300/4160 = 2500 to 4799 V
Table 3.B Power Stack Frame Specifications
Description
180 A
360 A
Input Voltages
(50/60 Hz)
1000 volts AC, 3 phase, +10% -15%
2300 volts AC, 3 phase, +10% -15%
3300 volts AC, 3 phase, +10% -15%
4160 volts AC, 3 phase, +10% -15%
Ambient Temperature
0°C to 40°C (32°F to 104°F)
Power Section
6 SCR at 1000 volts 12 SCR at 3300 volts
6 SCR at 2400 volts 12 SCR at 4160 volts
Repetitive Peak
Inverse Voltage Rating
1000 volts 4500 PIV 3300 volts 13000 PIV
2300 volts 6500 PIV 4160 volts 13000 PIV
Thermal Capacity
600% of FLA, 10 seconds (2 starts per hour, 5 minutes between starts)
450% of FLA, 30 seconds (2 starts per hour, 5 minutes between starts)
dv/dt Protection
R.C. Snubber Network
Maximum Heat
Dissipation (kW)
Start or Stop Cycle (@ 450% FLA)
Continuous
180 A
360 A
800 to 2499 V
7
13
.25
2500 to 4799 V
14
26
.25
Altitude
0 to 1000 m (0 to 3,300 ft)
(See Controller Deratings Table A-1 in Appendix A)
Net Weight
(Shipping)
1000 to 2300 V 116 kg (255 lbs)
3300 to 4160 V 125 kg (276 lbs)
Refer to Table 3.A for acceptable input voltage ranges.
For higher ambient conditions, contact Factory.
Specifications