54 Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Chapter 2 Installation
EMC Compliance
The following guidelines are provided for EMC installation compliance.
Enclosure
Install the product in a grounded metal enclosure.
Wiring
Wire in an industrial control application can be divided into three groups: power,
control, and signal. The following recommendations for physical separation
between these groups is provided to reduce the coupling effect.
Different wire groups should cross at 90° inside an enclosure.
Minimum spacing between different wire groups in the same tray should
be 16 cm (6 in.).
Wire runs outside an enclosure should be run in conduit or have shielding/
armor with equivalent attenuation.
Different wire groups should be run in separate conduits.
Minimum spacing between conduits containing different wire groups
should be 8 cm (3 in.).
For additional guidelines, please refer to Wiring and Ground guidelines,
publication DRIVES-IN001A-EN-P.
Wire earth ground to control terminal 14.
Use shielded wire for: PTC Input
Tac h Inp ut
Ground Fault Input
Terminate shielded wires to terminal 14.
Ground fault CT must be inside or within 3 m of metal enclosure.
ATTENTION: This product has been designed for Class A equipment. Use of the
product in domestic environments may cause radio interference, in which case,
the installer may need to employ additional mitigation methods.