Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013 181
ArcShield Unit Information Appendix D
Figure 80 - Cross-section of plenum extension, dimensions in mm [inches]
Plenum Exhaust
Considerations
The following options for locating the plenum exhaust are presented:
1. Plenum ducted to an area of the control room where arc gases are
permitted to escape, with plenum extensions (see Figure 81
, Figure 82 and
Figure 83
).
2. Plenum duct to outside of control room (see Figure 81
and Figure 82).
Plan the location where the plenum will exhaust. Ensure that:
There is no access to personnel while equipment is energized.
Area is free of flammable material or vapors
Ensure that adequate space is provided around the plenum exhaust, as outlined in
Figure 81
through Figure 83.
633 [25]
584 [23]
IMPORTANT
Be aware that equipment in the area of the plenum exhaust point will be
damaged or destroyed.