User guide
Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013 161
Parameter Information Appendix B
Group Parameter Description Parameter
Number
Units Min / Max Default
Settings
User
Settings
Ground Fault Gnd Flt Enable 72 Disable
Enable
Disable
Gnd Flt Level 73 A 1.0…5.0 2.5
Gnd Flt Delay 74 SEC 0.1…250.0 0.5
Gnd Flt Inh Time 75 SEC 2.25 10
Gnd Flt A Enable 76 Disable
Enable
Disable
Gnd Flt A Lvl 77 A 1.0…5.0 2.0
Gnd Flt A Dly 78 SEC 0…250 10
PTC PTC Enable 79 Disable
Enable
Disable
Phase Reversal Phase Reversal 80 Disable
Enable
Disable
Restart Starts Per Hour 81 0…99 2
Restart Attempts 82 0…5 2
Restart Delay 83 SEC 0…60 0
Comm Masks Logic Mask 87 8-bit binary
Data Links Data In A1 88
Data In A2 89
Data In B1 90
Data In B2 91
Data In C1 92
Data In C2 93
Data In D1 94
Data In D2 95
Data Out A1 96
Data Out A2 97
Data Out B1 98
Data Out B2 99
Data Out C1 100
Data Out C2 101
Data Out D1 102
Data Out D2 103
Motor Data Motor ID 104 0…65535 0
CT Ratio
(1)
105 1…1500
MV Ratio
(2)
106 1…10000
(1) Program the module for primary current rating (eg. 150:5 CT, program 150).
(2) Refer to Chapter 3,
Commissioning Procedure, to determine the appropriate setting.