User guide

160 Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Appendix B Parameter Information
Group Parameter Description Parameter
Number
Units Min / Max Default
Settings
User
Settings
Basic Set Up Stop Mode
(1)
32 Soft Stop
Linear Speed
SMB
(2)
Accu-Stop
(2)
Soft Stop
Stop Time 33 SEC 0…120 0
Basic Set Up/Accu-Stop Braking Current 35 % FLC 0…400 0
Preset SS/Accu-Stop Slow Speed Sel 39 SS Low
SS High
SS High
Slow Speed Dir 40 SS FWD
SS REV
SS FWD
Slow Speed Cur 41 % FLC 0…450 0
Slow Running Cur 42 % FLC 0…450 0
Accu-Stop Stopping Current 43 % FLC 0…400 0
Basic Set Up / Overload Overload Class 44 Disable
Class 10
Class 15
Class 20
Class 30
Class 10
Service Factor 45 0.01…1.99 1.15
Motor FLC 46 A 1.0…1000.0 1.0
Overload Reset 47 Manual Manual
Overload Overload A Lvl 50 % MTU 0…100 0
Underload Underload F Lvl 51 % FLC 0…99 0
Underload F Dly 52 SEC 0…99 0
Underload A Lvl 53 % FLC 0…99 0
Underload A Dly 54 SEC 0…99 0
Undervoltage Undervolt F Lvl 55 % V 0…99 80
(3)
Undervolt F Dly 56 SEC 0…99 1
Undervolt A Lvl 57 % V 0…99 0
Undervolt A Dly 58 SEC 0…99 0
Overvoltage Overvolt F Lvl 59 % V 0…199 0
Overvolt F Dly 60 SEC 0…99 0
Overvolt A Lvl 61 % V 0…199 0
Overvolt A Dly 62 SEC 0…99 0
Unbalance Unbalance F Lvl 63 % 0…25 0
Unbalance F Dly 64 SEC 0…99 0
Unbalance A Lvl 65 % 0…25 0
Unbalance A Dly 66 SEC 0…99 0
Jam Jam F Lvl 67 % FLC 0…1000 0
Jam F Dly 68 SEC 0…99 0
Jam A Lvl 69 % FLC 0…1000 0
Jam A Dly 70 SEC 0…99 0
Stall Stall Delay 71 SEC 0.0…10.0 0
(1) Pump option modules default to “Pump Stop.
(2) Brake module only.
(3) Do not set below 70.