User guide
138 Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Chapter 9 Troubleshooting
Figure 66 - Voltage Sensing Board
PB
To Interface Board
Ground Connections
Measure
11.3 kΩ
V rated Tap 1,3,5 Tap 2,4,6
1.5 kV 1.9 M 2.8 M
2.5 kV 3.7 M 5.6 M
4.8 kV 6.6 M 10.0 M
7.2 kV 11.2 M 16.9 M
Values: +/- 2%
L1 T1 L2 T2 L3 T3