User guide

118 Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Chapter 9 Troubleshooting
Table 23 - Miscellaneous Situations
(1)
Display Possible Causes Possible Solutions
Motor current and voltage fluctuates with steady load Motor
Erratic Load
Verity type of motor as a standard squirrel cage induction
motor
Check load conditions
Erratic operation Loose connections Shut off all power to controller and check for loose connections
Accelerates too fast Starting time
•Initial torque
Current limit setting
•Kickstart
Increase starting time
Lower initial torque setting
Decrease current limit setting
Lower kickstart time or turn off
Accelerates too slow Starting time
•Initial torque
Current limit setting
•Kickstart
Decrease starting time
Increase initial torque setting
Increase current limit setting
Increase kickstart time or turn off
Fan does not operate Wiring
•Failed fans(s)
Check wiring and correct if necessary
•Replace fan(s)
Motor stops too quickly with Soft Stop option Time setting Verify the programmed stopping time and correct if necessary
Motor stops too slowly with Soft Stop option Stopping time setting
Misapplication
Verify the programmed stopping time and correct if necessary
The Soft Stop option is intended to extend the stopping time
for loads that stop suddenly when power is removed from the
motor.
Fluid surges with pumps still occur with the Soft Stop option Misapplication Soft Stop ramps voltage down over a set period of time. In the
case of pumps, the voltage may drop too rapidly to prevent
surges. A closed loop system such as Pump Control would be
more appropriately suited.
Refer to Publication 150-911
Motor overheats Overload
Blocked ventilation
•Duty cycle
Allow motor to cool and reduce load.
Remove blockage and ensure motor is being adequately
cooled.
Preset Slow Speed and Accu-Stop options: Extended operation
at slow speeds reduces motor cooling efficiency. Consult motor
manufacturer for motor limitations.
Smart Motor Braking option: Check duty cycle. Consult motor
manufacturer for motor limitations.
Motor short circuit Winding fault Identify fault and correct
Check for shorted SCR; replace if necessary
Ensure power terminals are secure
Motor coasts when option stop is programmed Option not programmed
Current loop power supply not active
Incorrect control logic
Verify the option parameter settings and correct if necessary
Verify current loop power supply (refer to Power Supply Tests
on page 64 of Chapter 3)
Verify connections to module terminals 16 and 17 (refer
to Functional Description
on page 25 of Chapter 1)
(1) Various faults may occur if Parameter #15 is set to “Delta. It must be set to “Line” for all MV applications.
TIP
For Pump Stop issues, refer to Pump Application Considerations on page 20 of
Chapter 1.