User guide

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013 117
Troubleshooting Chapter 9
Table 19 - Motor Will Not Start – No Output Voltage to the Motor
Table 20 - Motor Rotates (but does not accelerate to full speed)
Table 21 - Motor Stops While Running
Table 22 - Irregular Starts
Display Possible Causes Possible Solutions
Fault displayed See fault description See Table 18
addressing fault conditions
Display is blank Control voltage is absent
Failed control module
Check control wiring and correct if necessary
Replace control module
Stopped 0.0 Amps Pilot devices
SMC Enable input is open at terminal 13
Terminal 16 is open
Start-Stop control has not been enabled for the human
interface module
Control voltage
Failed control module
Check wiring
Check wiring
Check wiring
Follow the instructions on page 104
to page 106 to
enable control capability
•Check control voltage
Replace control module
Starting Two or three power phases are missing Check power system
Check voltage sensing module and connections
Display Possible Causes Possible Solutions
Fault displayed See fault description See Tabl e 18
addressing fault conditions
Starting Mechanical problems
Inadequate Current Limit setting
Failed control module
Check for binding or external loading and correct
Check motor
Adjust the Current Limit Level to a higher setting
Replace control module
Display Possible Causes Possible Solutions
Fault displayed See fault description See Table 18
addressing fault conditions
Display is blank Control voltage is absent
Failed control module
Check control wiring and correct if necessary
Replace control module
Stopped 0.0 Amps Pilot devices
Failed control module
Check control wiring and correct if necessary
Replace control module
Starting Two or three power phases are missing
Failed control module
Check power system
Check voltage sensing module and connections
Replace control module
Symptom Possible Causes Possible Solutions
Bypass contactor closes before motor is up to speed Ramp time too short
Motor characteristics cause Up-to-Speed sensing too
early
Increase ramp time (parameter 18)
Adjust parameter 114 higher (no more than 5% at a
time)
Motor is up to speed but bypass contactor is delayed in
closing or does not close at all
•Ramp time too long
Motor characteristics cause Up-to-Speed sensing too
late or not at all
Decrease ramp time
Adjust parameter 114 lower (no more than 5% at a
time)
Rough start, erratic current, growling from the motor
(may see Line Faults)
Poor grounding of the power system or controller
Poor power quality, electrical noise, harmonics, VFD line
notching
Resolve ground issues
Adjust parameter 117 higher. Typical settings are 35 or
40. Not recommended to exceed 75 or go below 25.
During a Pump Stop, the motor takes more than 5 seconds
to begin to decelerate or takes longer than the
programmed stop time
Motor or pump characteristics do not match the default
setting
Adjust parameter 34 to between 20 and 30 (not
recommended to go above 40).
TIP
Although the default settings accommodate the vast majority of applications,
these tuning parameters may require more than one adjustment to achieve
optimal results. Some parameters are affected by motor loading and power
system conditions, so one setting may not be optimal for all conditions.