Chapter 9 Troubleshooting
Underload 23 Broken motor shaft
Broken belts, tool bits, etc.
•Pump cavitation
Repair or replace motor
•Check machine
Check pump system
Jam 24 Motor current has exceeded the user
programmed jam level
Correct source of jam
Check programmed time value
Stall 25 Motor has not reached full speed by the end of
the programmed ramp time
Correct source of stall
Phase Reversal 26 Incoming supply voltage is not in the expected
ABC sequence
Check power wiring
Disable protection if not needed
Comm Loss 27, 28, 29 Communication disconnection at the serial port Check for a communication cable disconnection
to the SMC Flex controller
Network 30, 31, 32 DPI network loss Reconnect for each DPI connected device
Ground Fault 33 Ground fault current level has exceeded
programmed values
Check power system and motor; correct if
necessary
Check programmed ground fault levels to
match application requirements
Excess Starts/Hr. 34 Number of starts in a one-hour period has
exceeded the value programmed
Wait an appropriate amount of time to restart
Consult factory if more than 2 starts per hour
are required
Power Loss
(1)
(with phase indication) 35, 36, 37 Missing supply phase (as indicated)
Loss of feedback
Check for open line (i.e., blown line fuse)
Check CT connections, replace Interface board
HAL_ID 38 Faulty interface Check ribbon cable connections between
interface board and control module
Check current loop system
Replace interface board
NVS Error 39 Data entry error Check user data and perform a User Store
function
Replace control module
Line Loss 41, 42, 43 Line Distortion
High impedance connection
Check supply voltage for capability to start/stop
motor
Verify system grounding (refer to Resistance
Checks on page 68 of Chapter 3)
Check for loose connections on line side or
motor side power wires
V24 Loss 45 Internal power supply problem Cycle control power to reset the control module
If Fault persists, replace control module
V Control Loss 46 Internal sense circuit problem Cycle control power to reset the control module
If Fault persists, replace control module
Option Input 1 48 External Fault Check programming of Parameter 132
Check status of device connected to Input 1
Option Input 2 49 External Fault Check programming of Parameter 24
Check status of device connected to Input 2
System Faults 128 to 209 Control module internal fault Cycle control power to reset the control module
If fault persists, replace control module
(1) Prestart fault indication
Display Fault Code Possible Causes Possible Solutions