Owner manual

MRB01X
S
200
5
Issue 4
3
Triguard
SC300E MRB01XS Remote Bus Extender Slave Module
SPECIFICATION
Model
MRB01XS
Fibre
optic
ports
1 transmit,
1 receive
Fibre
optic
cable
(not
supplied)
Multimode
62.5/125;m cable
& 50/125;m
cable
(ST
connector
to
ST
connector)
Maximum
drive
loss
50/125;m cable
= 9dB
62.5/125;m cable
= 16dB
Indicators
Health,
Tx,
Rx
Module
power
consumptin
3W
Overall
size
(mm)
Overall
size
(inches)
400(9U)H
x 397L
x 28W
15.75H
x 15.63L
x 1.1W
Weight
1.0kg
ENVIRONMENTAL
SPECIF
ICATIONS
The
maximum
ambient
temperature
measured
at
the
hottest
point
within
the
Triguard
system
shall
not
be
greater
than
60
degrees
centigrade.
Temperature
operating:
+5°C
to
+60°C
Temperature
storage:
-
25°C
to
+70°C
Humidity:
5%
to
95%
non
-
condensing
at
ambient
<40°C
Certification:
General
Certification:
Ref.
SC300E
TMR
Product
Guide
(ref
008
-
5209)