Instruction Manual
7
Table 2.D - DĆC MOTOR/CONTROLLER/TRANSFORMER SPECIFICATIONS
CO
NTR
O
LLER
DĆC
OPTIONAL
POWER
TRANSFORMER
CONTROLLER
MODEL NUMBERS
AĆC DĆC
D
Ć
C
ARM.
DĆC
FIELD
AMP.
MAX
POWER
SUPPLY
MAXIMUM
kVA
FULL
LOAD
ENCLOSED CHASSIS
HP
VAC
AC
AMPS
(RMS)
DC
ARM.
(VOLTS)
ARM
.
AMPS
(avg.)
FIELD
VOLTS
MAX.
(optional)
SUPPLY
CAPACITY
➁
kVA
Per Phase
LOAD
kVA
14C30 14C40 1/4
1/3
1/2
3/4
115
115
115
115
ă3.5
ă5.2
ă7.0
10.5
ă90
ă90
ă90
ă90
ă2.5
ă3.7
ă5.0
ă7.5
100
100
100
100
3.0
3.0
3.0
3.0
1000
1000
1000
1000
40
40
40
40
ă0.75
ă0.75
1.0
1.5
14C31 14C41 1/2
3/4
1
1Ć1/2
230
230
230
230
ă3.5
ă5.2
ă7.0
10.5
180
180
180
180
ă2.5
ă3.7
ă5.0
ă7.5
200
200
200
200
3.0
3.0
3.0
3.0
1000
1000
1000
5000
40
40
40
40
ă1.0
ă1.5
ă2.0
ă3.0
14C32 14C42 2
3
230
230
14.0
21.0
180
180
10.0
15.0
200
200
3.0➀
3.0➀
5000
5000
40
40
ă5.0
ă5.0
14C33 14C43 5 230 35.0 180 25.0 200 3.0➀ 5000 40 10.0
➀ Standard
➁
Maximum permissible available symmetrical RMS fault current.
Section 3
INSTALLATION
3.0 General Ċ This Section outlines the procedures that
are to be followed in order to properly plan, layout, asĆ
semble and install a Regenerative MinPak Plus controlĆ
ler.
The dĆc motor should be installed and wired in accorĆ
dance with installation instructions supplied with each
drive.
There are certain precautions that should be kept in mind
before planning begins. They should be considered a
general checklist which, if followed, will minimize installaĆ
tion problems and decrease assembly time. As a user
aid, they are listed here.
DANGER
THIS UNIT SHOULD BE INSTALLED, ADJUSTED
AND SERVICED BY QUALIFIED ELECTRICAL
MAINTENANCE PERSONNEL FAMILIAR WITH
THE CONSTRUCTION AND OPERATION OF
THIS TYPE OF EQUIPMENT. THEY SHOULD
ALSO BE FAMILIAR WITH THE POTENTIAL
HAZARDS INVOLVED. IF THIS WARNING IS NOT
OBSERVED, PERSONAL INJURY OR EQUIPĆ
MENT DAMAGE MAY RESULT.
DANGER
BE ABSOLUTELY CERTAIN THAT A GROUND
WIRE FROM THE INCOMING AĆC POWER LINE
IS PROPERLY CONNECTED TO THE CHASSIS
GROUND TERMINAL PROVIDED. WITHOUT
PROPER GROUNDING, PERSONAL INJURY
MAY OCCUR.
WARNING
THE USER IS RESPONSIBLE FOR CONFORMĆ
ING WITH THE NATIONAL ELECTRICAL CODE
WITH RESPECT TO MOTOR, CONTROLLER
AND OPERATOR DEVICE INSTALLATION, WIRĆ
ING AND STARTĆUP. THE USER IS ALSO REĆ
SPONSIBLE FOR UNDERSTANDING AND APĆ
PLYING ALL OTHER APPLICABLE LOCAL
CODES WHICH GOVERN SUCH PRACTICES AS
WIRING PROTECTION, GROUNDING. DISCONĆ
NECTS AND OVERCURRENT PROTECTION.
3.1 Planning, Layout Guidelines Ċ Before actual asĆ
sembly and installation begins, careful layout planning
must be made. This Paragraph lists recommended planĆ