User Manual Instruction Manual
A:4
Table AĆ4. Isolation Transformer Specifications (Continued).
HP
kVA Primary Vac Secondary
Vac
Reliance Part
Number
2 5.0 230/460 230 77530Ć16G
575 230 77530Ć17G
3Ć5 10.0 230/460 230 77530Ć16H
575 230 77530Ć17H
NOTE: Smaller drives through 3/4 HP @ 115 VAC and 2.0 HP @ 230 VAC may be used with permanent magnetic field motors, and those drive
models are supplied without a DĆC field supply.
Table AĆ5. Fuse Requirements.
Dual Element Class
K5, RK5, 250VAC Fuse
HP
AĆC Line
Volts
Quantity AMP
Reliance Part
Number
1/4Ć3/4 115 1
1
15 64676Ć1W
1/2Ć1 1/2 230 2 15 64676Ć1W
2Ć3 230 2 30 64676Ć1Z
5 230 2 50 64676Ć1AD
1
Install fuse in input line L1 (hot line).
Table AĆ6. Controller Modification Kits.
Kit Name
Kit Model
Number
Controller
Modification
?
1
Options Required
Instruction
Manual
Local Operator Station Faceplate 14C201 thru 8 no None -
Blank Operator Station
Faceplates
14C200 no Reliance Remote Operator Control Station -
Remote Operator Adapter Kit 14C220 yes (See Blank Faceplate, just above.) -
Double Pole Circuit Breaker 14C210 thru 13 yes None -
Auxiliary Mounting Bracket
2
14C209 no
Always used with some other option; inĆ
cluded with Field Supply Kit.
-
Reversing Contactor
14C217 &
14C218
yes
FORWARD/REVERSE selector switch on
Operator Station (See table 6.B.)
D2Ć3307
Auxiliary M Contact 14C219 no Auxiliary Mounting Bracket
2
-
Tachometer Feedback 14C221 yes None DĆ3969
Voltage/Tachometer Follower 14C223 yes May need AUTO/MANUAL selector switch DĆ3971
Torque Taper 14C224 yes None -
Test Meter Adapter 14C225 no None DĆ3970
Automatic Reversing 14C226 no
Auxiliary Mounting Bracket
Reversing Contactor Kit
-
Dynamic Braking 14C214 thru 16 no None -
Instrument Interface/
Preset Speed
14C222 yes
If preset speed only, may need AUTO/
ąăMANUAL switch.
If follows process controller, may need
ąăAUTO/MANUAL switch.
DĆ3967
Master Isolated Reference
Receiver
14C229 yes Master Isolated Reference Transmitter -
Dancer Follower 14C230 yes None DĆ3966
1
Modification here means that some work such as jumper placement, resistor clipping, or wiring reconnection must be performed.