Owner's manual

Triguard
SC300E
MDO32BNS
32-Channel Digital Output Module
(MDO32BNS)
Issue
7
October
2005
The
Digital
Output
Module
provides
the
output
control
interface
between
the
SC300E
processing
environment
and
up
to
32
common
low
voltage
field
devices.
All
field
outputs
from
the
module
are
galvanically
isolated
from
the
system.
Circuit
triplication
and
voting
procedures
make
the
module
single
-
fault
tolerant
and
latent
testing
ensures
that
the
failure
of
a normally
‘ON
(energised)
or
‘OFF’
channel
will
be
recognised
and
reported
to
the
system.
Front
panel
indicators
show
the
state
of
all
channels,
the
circuit
‘on
-
line’
status
and
the
health
of
the
module.
The
module,
which
is
compatible
with
‘dual
-
slot
hot
repair’,
can
be
fitted
in
any
of
the
ten
I/O
slots
in
the
SC300E
chassis,
‘wrong
slotting’
is
prevented
by
physical
coding.
The
SC300E
system
software
identifies
the
module
via
a built
-
in
hardware
identifier.
Channel
outputs
leave
the
module
via
the
DIN
41612
‘rear
plug
-
up’
system
on
the
chassis
backplane.
This
document
is
intended
to
provide
a general
understanding
of
the
function
of
the
Digital
Output
Module
sufficient
to
enable
basic
maintenance
operations
to
be
effected
in
the
field.
008-5102