User guide

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012 91
Troubleshooting the Kinetix 6000M System Chapter 7
IDM Unit Status Indicators
IDM unit fault descriptions and actions start on page 95.
Figure 37 - IDM Unit Indicators
Port 1
Port 2
Status of the
EtherNet/IP
ports
Off Port is not connected
Flashing Green Port is connected and communication is occurring
Solid Green Port is connected, but no communication is not occurring
(1) A reset or cycling the power may clear a recoverable fault (depending on the state of the IDM). An unrecoverable fault will require
power cycling and/or modifying the hardware configuration while unpowered to clear the fault.
Indicator Indication Description
Network
Status (N)
Provides communication
status for the IDM unit.
Off Communication is not active
Flashing green
(1 s interval)
Communication is being established
Solid green Communication has been established
Solid red A duplicate address exists
Fast flashing green
(0.5 s interval)
Firmware update in process
Slow flashing green
(2 s interval)
Firmware update in process on another IDM
Drive
Status (D)
Provides general status
for the IDM unit.
Off Power is not applied
Flashing green Module is in standby mode
Solid green Module is operating
Flashing red Recoverable fault has occurred
(1)
(1) A reset or cycling the power may clear a recoverable fault (depending on the state of the IDM). An unrecoverable fault will require
power cycling and/or modifying the hardware configuration while unpowered to clear the fault.
Solid red Unrecoverable (or hardware) fault has occurred
(1)
Indicator Indication Description
D
S1
S10
N
12
3
Drive Status (D)
Network Status (N)