User guide

90 Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Chapter 7 Troubleshooting the Kinetix 6000M System
Interpret Status Indicators
When a fault condition is detected, the appropriate status indicator will
illuminate (IDM unit or IPIM module) and the IPIM module will annunciate
the fault on its front panel display. Refer to Figure 36
for IPIM status indicator
descriptions and Figure 37
for IDM unit indicators.
IPIM Module Status Indicators
IPIM module fault descriptions, types and actions start on page 94.
Figure 36 - IPIM Display and Status Indicators
Indicator Indication Description
Control
Bus
Status of the
Control Bus
Off Control bus is not present
Solid Green Control bus is present
Solid Red A fault has occurred
Module
Status
IPIM Module
Status
Off Power is not applied to the module
Flashing Green Module is in Standby mode - configuration may be required
Solid Green Module is operating correctly
Flashing Red A recoverable fault has occurred
(1)
Solid Red An unrecoverable fault has occurred
(1)
Alternating Green/Red Self-test mode during powerup
Network
Status
Network Status Off Not powered or no IP address
Flashing Green No connections, but an IP address has been obtained
Solid Green An established connection exists
Flashing Red A connection has timed out
Solid Red Duplicate IP is present
Alternating Green/Red Self-test mode during powerup
DC Bus Status of the DC
Bus
Off DC Bus is not present
Flashing Green DC bus is present and all IDM units are disabled
Solid Green DC bus is present and at least one IDM unit is enabled
IPIM
01
07
13
02
08
14
03
09
15
04
10
16
05
11
06
12
Info Tools
Control Bus
Module Status
Network Status
DC Bus
Port 1
Port 2
Control Bus
Module Status
Network Status
DC Bus
Port 1
Port 2