User guide

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012 115
Appendix C
Upgrading the Kinetix 6000M System Firmware
This appendix provides procedures for upgrading firmware for the
Kinetix 6000M integrated drive-motor (IDM) units and IDM power interface
modules (IPIM).
Upgrading firmware for the Kinetix 6000M system is done by using
ControlFLASH software. The procedure for upgrading the IDM units uses the
sercos interface, similar to axis modules. However, upgrading firmware on the
IPIM module is accomplished over the EtherNet/IP network.
Before You Begin
You need the following software and information before you begin.
Topic Page
Before You Begin 115
Configure Logix Communication 116
IPIM Module Firmware Upgrade 117
IDM Unit Firmware Upgrade 122
Verify the Firmware Upgrade 126
Description Cat. No.
Firmware Revision or
Software Version
RSLogix 5000 software 9324-RLD300NE 20.01
(2)
or later
(2) Version 20.00 may be used if the motion database has been updated.
ControlLogix sercos module 1756-MxxSE 20.007 or later
CompactLogix sercos module 1768-M04SE 20.007 or later
SoftLogix sercos PCI card 1784-PM16SE 20.007 or later
RSLinx® software 2.59 or later
ControlFLASH software kit
(1)
(1) Download the ControlFLASH kit from http://support.rockwellautomation.com/controlflash. Contact Rockwell Automation Technical
Support at (440) 646-5800 for assistance.
For more ControlFLASH information (not drive specific), refer to the ControlFLASH Firmware Upgrade Kit Quick Start, publication
1756-QS105
.
From website
Catalog number of the targeted IPIM module and IDM unit you want to upgrade
Network path to the targeted IPIM module and IDM unit.
Control power must be present prior to upgrading your IPIM module or IDM
units.
ATTENTION: To avoid personal injury or damage to equipment during the
firmware upgrade due to unpredictable motor activity, do not apply 3-phase AC
or common-bus DC input power to the IAM module.