User Manual Version 2.0 Owner manual

Troubleshooting the Drive
10-5
F41 Phase UV
Short
N Excessive current has
been detected
between these two
output terminals.
Check the motor and
drive output terminal
wiring for a shorted
condition.
Replace drive if fault
cannot be cleared.
F42 Phase UW
Short
F43 Phase VW
Short
F48 Params
Defaulted
N The drive was
commanded to write
default values to
EEPROM.
Clear the fault or cycle
power to the drive.
Program the drive
parameters as needed.
F63 SW
OverCurrent
Y Programmed SW
Current Trip (A098)
has been exceeded.
Check load requirements
and SW Current Trip
(A098) setting.
F64 Drive
Overload
N Drive rating of 150%
for 1 minute or 200%
for 3 seconds has been
exceeded.
Reduce load or extend
Accel Time.
F70 Power Unit N Failure has been
detected in the drive
power section.
Cycle power.
Replace drive if fault
cannot be cleared.
F80 SVC
Autotune
N The Autotune function
was either cancelled
by the user or failed.
Restart procedure.
F81 Comm Loss N RS485 port stopped
communicating.
If module was not
intentionally
disconnected, check
wiring to the port.
Replace wiring, port
expander, module, or
complete drive as
required.
Check connection.
A module was
intentionally
disconnected.
Turn off using Comm
Loss Action (A105).
Table 10.1 – Fault Descriptions and Corrective Actions (Continued)
No. Fault
Auto-Reset
1
?
Description Action