Owner manual
Troubleshooting the PROFIBUS Module and Network 9-3
9.1.2 MS Status Indicator
Table 9.2 – MS Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is not
powered.
• Securely connect the module
to the MD65 drive using the
ribbon cable.
• Apply power to the drive.
Flashing
Red
The module has
faults or a drive is
missing in Multi-
Drive mode.
• Clear faults in the drive.
• Disconnect additional MDI
peripheral and cycle power to
the drive.
• If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.
• If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.
• For Multi-Drive mode,
determine which drive is
missing or faulted. Check
cabling and configuration
settings.
Solid
Red
The module has
failed the hardware
test.
• Cycle power to the drive.
• Replace the module.
Flashing
Green
The module is
operational but is not
transferring I/O data.
• Place the scanner in RUN
mode.
• Configure the module for the
program in the controller.
• Program the controller to
recognize and transmit I/O to
the module.
Solid
Green
The module is
operational and
transferring I/O data.
• No action.