Owner manual

9-2 PROFIBUS Communications Module
9.1.1 DRIVE Status Indicator
Table 9.1 – DRIVE Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is not
powered or is not
connected properly to
the drive.
Securely connect the module
to the drive using the ribbon
cable.
Apply power to the drive.
Flashing
Red
The module is not
receiving a ping
message from the
drive.
Verify that cables are
securely connected.
Cycle power to the drive.
Solid
Red
The drive has refused
an I/O connection from
the module.
Another MDI peripheral
is using the same MDI
port as the module.
Important: Cycle power to the
product after making following
correction:
Verify that all MDI cables on
the MD65 drive are securely
connected and not damaged.
Replace cables if necessary.
Check the Events, replace
the module with a compatible
Reliance Electric branded
product (MDCOMM-PBUS).
Flashing
Green
Not Used
Solid
Green
The module is properly
connected and is
communicating with the
drive.
No action.
Solid
Orange
The module is booting. Wait until boot program is
complete.
Flashing
Orange
The module is in flash
mode (SW8 down).
Application Failure
Wait until Firmware Update
is complete, then switch
SW8 to 1.
Download Application code.