5-2 Serial Converter Module (MDCOMM-232)
5.1.1 Diamond Status Indicator
!
ATTENTION: If the Serial Con v erter is transmitting control
I/O to the product (indicated by a steady green diamond LED
on the Serial Conv erter), the product may fault when y ou
remove or reset the Serial Conver ter. Determine how your
product will respond before removing or resetting a Serial
Conv erter. F ailure to observe this precaution could result in
bodily injury and/or damage to equipment.
Table 5.1 – Diamond Status Indicator: State Definitions
State Cause Corrective Action
Off Serial Converter is not
powered or is in Flash
programming mode.
Securely connect cables.
Apply power to the product.
Wait while Flash is in progress.
Flashing
Green
Serial Conv erter is
operating and not
transmitting control I/O.
No action required.
Removing or resetting the Serial
Converter will not cause a serial fault
in the product.
Steady
Green
Serial Conv erter is
operating and is or was
transmitting control I/O.
No action required.
Removing or resetting the Serial
Converter may cause a serial fault in
the product.
Flashing
Red
The product has not
acknowledged the
Serial Con verter.
Securely connect cables.
Make sure Adapter Cfg (01) is set to
Auto.
Steady
Red
Link failure.
Securely connect cables.
Replace the cable.
Cycle power to the product.
Orange Brand lock. Contact Rockwell Automation
Technical Support.