2.
Operate
the
On/Off
Line
Request
switch
on
the
new
module.
Ascertain
that
the
three
On
Line
LEDs
on
the
new
module
illuminate
for
one
second,
extinguish
for
one
second
and
then
illuminate
permanently
as
the
LEDs
on
the
old
module
extinguish.
This
se
quence
indicates
that
the
new
module
has
been
put
on
line
and
the
old
module
taken
off
line.
If
the
LEDs
on
the
new
module
do
not
illuminate
either
the
first
or
second
time
or
fail
to
remain
illuminated,
the
new
module
must
be
regarded
as
faulty.
The
old
module’s
LEDs
should
remain
illuminated
indicating
that
it
is
still
on
line.