User Manual
Enclosed Resistor Modules, Enclosed Transistor Modules
11
Snubber Transistor Kits (M3575TH__, M3575TL__)
The figure below depicts the breakdown of the Enclosed Transistor kit part number.
Enclosed Transistor Braking Unit Status Indicators
Braking units have the following status indicators:
• DC BUS: A green LED that turns on when the DC bus voltage is equal to or greater than 90 VDC.
• ACTIVE BRAKING: A red LED that turns on when the dynamic braking transistor turns on. Note that if this
indicator is on continuously, the AC line voltage may be high. Use an input transformer to reduce the
incoming AC line voltage to the AC drive or consult your local Rockwell Automation - Reliance Electric sales
office for assistance.
Enclosed Transistor Braking Unit Fault Outputs
Enclosed Transistor Braking units have one normally-closed contact (NC) rated at 2 amps, 125 VDC or
125 VAC that opens on the following fault conditions:
• loss of DC bus voltage
• open load
• Overtemperature
• transistor failure
Table 4 – Enclosed Transistor Kit Ratings
AC Line
Voltage
Braking Kit
Model Number Amps DC RMS
Minimum Load
Resistance (
Ω)
Enclosure
Type
230 M3575TL15 15 25 M3
M3575TL30 30 12.5
M3575TL60 60 6.25 M4
460 M3575TH15 15 50 M3
M3575TH30 30 25
M3575TH75 75 10 M4
M3575TH125 125 6 B4
M3575TH150 150 5
M3575TH200 200 3.75 B7
M3575TH300 300 2.5
M3575T L 30
Base Model Number
AC Voltage Rating
L = 230 VAC
H = 460 VAC
DC Current Rating