A-2 Supplemental Drive Information
Environment
(continued)
Atmosphere: Important: Drive must not be installed in an area
where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going
to be installed for a period of time, it must be stored in
an area where it will not be exposed to a corrosive
atmosphere.
Relative Humidity: 5 to 95% non-condensing
Shock: 15G peak for 11 milliseconds duration (± 1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak
Electrical Voltage Tolerance: For full power and operating range, see the PowerFlex
700S High Performance AC Drive — Phase II Control
User Manual (Publication No. 20D-UM006…),
Appendix E.
Frequency Tolerance: 47-63 Hz.
Input Phases: Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
Displacement Power Factor: 0.98 across entire speed range.
Efficiency: 97.5% at rated amps, nominal line volts.
Max. Short Circuit Rating: 100,000 Amps symmetrical.
Actual Short Circuit Rating: Determined by AIC rating of installed circuit breaker.
Motor Lead Lengths: 76 meters (250 feet) total
Control Method: Sine coded PWM with programmable carrier
frequency. Ratings apply to all drives (refer to the
Derating Guidelines in the PowerFlex Reference
Manual). The drive can be supplied as 6 pulse or 12
pulse in a configured package.
Carrier Frequency: 2, 3 or 4 kHz. Drive rating based on 4 kHz.
Output Voltage Range: 0 to rated motor voltage
Output Frequency Range: 0 to 400 Hz.
Speed Control: Speed Regulation - without feedback
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Regulation - with feedback
0.001% of base speed across 120:1 speed range
1000:1 operating range
300 rad/sec bandwidth
Torque Regulation: Torque regulation - without Feedback
± 10%, 600 rad/sec bandwidth
Torque regulation - with Feedback
± 5%, 4400 rad/sec bandwidth
Selectable Motor Control: Field Oriented Control with and without a feedback
device and permanent magnet motor control.
Stop Modes: Multiple programmable stop modes including - Ramp,
Coast, and Current Limit.
Accel/Decel: Independently programmable accel and decel times,
adjustable from 0 - 6553.5 seconds in 0.01 second
increments.
S-Curve Time Adjustable from 0.5 to 4.0 seconds
Intermittent Overload: 110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds
Current Limit Capability: Proactive Current Limit programmable from 20 to
160% of rated output current. Independently
programmable proportional and integral gain.
Electronic Motor Overload Protection: Class 10 protection with speed sensitive response.
Investigated by U.L. to comply with N.E.C. Article 430.
U.L. File E59272, volume 12.
Category Specification