Essential Requirements for CE Compliance
Conditions 1-5 listed below must be satisfied for LPM20 drives to meet the
requirements of EN61800-3:
1. Standard LPM20 CE compliant drive.
2. Grounding as described in Grounding the Drive
on page 1-13.
3. Output power wiring to the motor, and all control/signal wiring must use
braided shielded cable with a shield coverage of 75% or greater, or metal
conduit.
4. The shields of all shielded cables must be terminated with the proper
connectors to chassis/earth.
5. Motor cables must not exceed 20 meters (65.6 feet) in length.
C-Tick Conformity
Compliance of LPM20 drives with the Australian Radiocommunications
Act of 1992 has been demonstrated through compliance with EN61800-3.
Both the General Notes and the Essential Requirements for CE Compliance
provided above apply to C-Tick compliance for LPM20 drives.