Installation/Wiring 1-17
Installing Input Power
Wiring
This section describes incoming line components and how to install them.
Installing Transformers and Reactors (Not Recommended)
The LPM20 AC drive may be used on distribution systems with 100,000
amps or less symmetrical fault current capacity. The Drive Input
components consists of a 3% line reactor and a harmonic line filter.
Additional input inductance is not recommended.
Figure 1.8 Drive Input Wiring
NOTE: Proper torque for Line Side Lugs is labeled on the circuit breaker.
L1 L2 L3
Circuit Breaker
Line Side Lugs
Ground Lug
2-600 MCM
Torque Label for
Line Side Lugs