Quick Start User guide
18 Rockwell Automation Publication IASIMP-QS028A-EN-P - July 2012
Chapter 1 Prepare the PowerFlex 40 Drive Hardware
3. Adjust the rate switches the same
way as the node switches
described in step 2
to set the
baud rate.
4. Use the following table to set the
communication rate.
This quick start uses Autobaud.
Rate Switch
78
125 Kbps 0 0
250 Kbps 1 0
500 Kbps 0 1
Autobaud 1 1
2
1
8
3
4
5
6
7
RATE
U
P =
O
PEN =
1
8
7
Autobaud Rate