Chapter 9
Frame 4 drives (firmware version 2.x) only:
Figure 69 - Rectifier Control (100) Frame 4
The actual state of the rectifier.
Frame 3 drives (firmware version 1.x) only:
Figure 70 - Rectifier Status (101) Frame 3
101 Rectifier Status
Range: See Figure 70
Default: N/A
Access: 0 Path: Dynamic Control > Control and Status
See also: inverter 34
IMPORTANT
This parameter is used for communication between the inverter and the
rectifier. Do not write to this parameter using VS Utilities, DriveExplorer, or an
OIM. Its value changes according to the operational state of the drive.
x
0011234567891112131415
x =Reserved
Bit #
Shunt Trip
Nibble 1Nibble 2Nibble 3Nibble 4
x
x
xx
xx
x
Enable Rectifier
Close Pre-charge
Reset Rectifier Fault
Inverter Fault
Network Loss
DC Bus Limit
Extend
xxxx
0011234567891112131415
x =Reserved
Bit #
OK to Run Inverter
Rectifier Running
Rectifier Faulted
Rectifier in Limit
Rectifier Synchronized
Rectifier Phased ACB
Rectifier at Voltage
Rectifier Regenerating
Fault Reset Echo
Nibble 1Nibble 2Nibble 3Nibble 4
Rectifier Carrier Sync
Bit 0 Indicates OK to Run
Standby