Owner's manual
Table Of Contents
- Front Cover
- Important User Information
- Summary of Changes
- Table of Contents
- Introduction
- About the Drive
- Identifying the Drive by Cabinet Assembly ID Number
- LiquiFlo 2.0 Drive Component Locations
- Identifying the Power Module by Model Number
- AC Line I/O Board Description (Frame 3 Only)
- Standard I/O Board Description (Frame 3 Only)
- Combined I/O Board Description (Frame 4 Only)
- DPI Communication Ports
- Optional Equipment
- Planning the Installation
- Mounting The Power Module and Grounding the Drive
- Installing Input and Output Power Wiring
- Completing the Installation
- Using the Start-up Routines
- Programming Basics
- Parameter Descriptions
- Troubleshooting the Drive
- Verify that the DC Bus Capacitors are Discharged Before Servicing the Drive
- Determining Drive Status Using the Status LEDs
- About Alarms
- About Faults
- Diagnostic Parameters
- Common Symptoms and Corrective Actions
- Replacement Parts
- Board Replacement, Firmware Setup Procedures
- Troubleshooting the Drive Using the OIM
- Checking the Power Modules with Input Power Off
- Technical Specifications
- Using the OIM
- Installing and Removing the OIM
- Display Description
- OIM Menu Structure
- Powering Up and Adjusting the OIM
- Selecting a Device in the System
- Using the OIM to Program the Drive
- Monitoring the Drive Using the Process Display Screen on the OIM
- Displaying and Changing the OIM Reference
- Customizing the Process Display Screen
- Customizing the Function Keys
- Controlling the Drive From the OIM
- LiquiFlo 2.0 Drive Frame 3 Wiring Diagrams
- LiquiFlo 2.0 Drive Frame 4 Wiring Diagrams
- Index
- Back Cover

170 Rockwell Automation Publication D2-3518-3 - May 2013
Chapter 9
Defines the allowed power dip time that will not cause a Ride Thru Abort fault
(fault 221).
• Setting a value of 0 generates a fault on a loss of a single line cycle.
• Setting a value of 0.10 allows line synchronization to be lost for 100 msec
before a fault is generated.
A fault is also generated if the bus voltage drops below the power loss threshold
before the ride-through time has elapsed.
The commanded state of the rectifier.
Frame 3 drives (firmware version 1.x) only:
Figure 68 - Rectifier Control (100) Frame 3
65 Ride Through Sec
Range: 0.00...60.00 seconds [x.xx seconds]
Default: 1.00
Access: 0 Path: Configuration > AC Line
See also: 64, inverter 184, 185
100 Rectifier Contrl
Range: See Figure 68 and Figure 69
Default: N/A
Access: 0 Path: Dynamic Control > Control and Status
See also: inverter 33
IMPORTANT
This parameter is used for communication between the inverter and the
rectifier. Do not write to this parameter using VS Utilities, DriveExplorer, or an
OIM. Its value changes according to the operational state of the drive.
xxx
0011234567891112131415
x =Reserved
Bit #
AC Line I/O: Dig. Output 1
AC Line I/O: Dig. Output 2
AC Line I/O: Dig. Output 3
AC Line I/O: Dig. Output 4
AC Line I/O: Dig. Output 5
AC Line I/O: Dig. Output 6
Close Pre-charge
Enable Rectifier
Reset Recifier Fault
Inverter Fault
Network Loss
DC Bus Limit
Extend
Nibble 1Nibble 2Nibble 3Nibble 4