Owner manual

A-2
LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table A.2 – Environmental Conditions
Condition Specification
Operating Temperature (inside an enclosure)
0°C to 55°C
*
(32°F to 131°F)
*
User-supplied cabinet air cooling system must provide adequate heat dissipation to maintain an internal
temperature not to exceed 55°C. Refer to table 2.1 for drive air watts loss.
Storage Temperature (Ambient) -40°C to 65°C (−40°F to 149°F)
Humidity 5% to 95% (non-condensing)
Table A.3 Terminal Strip Input Specifications
Signal Type Terminal(s) Specification
Speed Reference Input 12-15 10 V (@ 50 K ohm input
impedance or 20 mA)
Digital Inputs (1 - 8) 16 +24 VDC Isolated Supply
17 Remote/Local (Default)
18 Ramp1/Ramp2 (Default)
19 Forward/Reverse
(Default)
20 Function Loss
21 Run/Jog
22 Reset
23 Stop
24 Start
Table A.4 – Terminal Strip Output Specifications
Signal Type Terminal(s) Specification
Analog Output 10 -11
scaled signal
0-10 VDC or 4-20 mA
No Connection 26 There is no connection to
terminal 26.
Common 27 +24 VDC common