LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table 7.3 – Analog Output Connections (Terminals 10 and 11)
Terminal # Signal
10 Analog Meter Output
11 Regulator Common
Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the
setting of jumper J17 on the Regulator board. The analog output must also be
programmed via parameter P.012 for an indication of speed and direction or percent
of torque.
Table 7.4 – Analog Speed/Torque Reference Connections (Terminals 12-15)
Terminal # Signal
12 Isolated Reference Voltage
13 VDC Speed/Torque Reference
14 mA Speed/Torque Reference
15 Isolated Reference Common
Notes: The analog speed/torque (P.008/U.000) reference is either +/-10 VDC or
+/-20 mA, as determined by the setting of jumper J4 on the Regulator board. The
analog reference can be adjusted using parameters P.009, P.010, and P.011.