E-2 LiquiFlo AC Drive, Software Reference Version 6.4
Summary of Options for P.007, P.008, and r.030
Option Comparison Tables
P.007 Options P.008 Options
DIGIN 6 DIGIN 7 DIGIN 8 DIGIN 6 DIGIN 7 DIGIN 8
0 = FWD/REV RAMP 1/2 REM/LOC 0 = Not used Not used Not used
1 = Not used FWD/REV RAMP 1/2 1 = MOP ↑ MOP ↓ Not used
2 = Not used FWD/REV REM/LOC 2 = 2 Presets Not used Not used
3 = Not used RAMP 1/2 REM/LOC 3 = 4 Presets Not used
4 = Not used Not used FWD/REV 4 = 8 Presets
5 = Not used Not used RAMP 1/2 5 = Analog ref
and 1 preset
Not used Not used
6 = Not used Not used REM/LOC
7 = Not used Not used Not used 6 = Analog ref and 3 presets Not used
8 = FWD/REV TRQ/SPD REM/LOC 7 = Analog ref and 7 presets
9 = Not used TRQ/SPD REM/LOC
10 = Not used TRQ/SPD FWD/REV
11 = Not used TRQ/SPD RAMP 1/2
12 = Not used Not used TRQ/SPD
r.030 Options
RMI DIGIN 1 RMI DIGIN 2 RMI DIGIN 3 RMI DIGIN 4
0 = Ref 1/2 A/F Aux 2 Aux 1
1 = Ref 1/2 A/F Aux 2 PI Enable
2 = Ref 1/2 MOP ↑ MOP ↓ Aux 1
3 = Ref 1/2 MOP ↑ MOP ↓ PI Enable
4 = Ref 1/2 2 Presets Aux 2 Aux 1
5 = Ref 1/2 2 Presets Aux 2 PI Enable
6 = Ref 1/2 4 Presets 4 Presets Aux 1
7 = Ref 1/2 4 Presets 4 Presets PI Enable
8 = Ref 1/2 8 Presets 8 Presets 8 Presets
If P.007 =
Acceptable
P. 0 0 8
Values
If r.030 =
Acceptable
P.008
Values
If P.008 =
Acceptable
P. 0 0 7
Values
If P.008 =
Acceptable
r.030
Values
0 0 0 0-6 (all) 0 0-12 (all) 0 0-8 (all)
1 0, 2, 5 1 0-6 (all) 1 4-7, 12 1 0, 1, 4-8
2 0, 2, 5 2 0, 2-6 2 1-7, 9-12 2 0-3
3 0, 2, 5 3 0, 2-6 3 4-7, 12 3 0-3
4 0-3, 5, 6 4 0, 1 4 7 4 0-3
5 0-3, 5, 6 5 0, 1 5 1-7, 9-12 5 0-3
6 0-3, 5, 6 6 0, 1 6 4-7, 12 6 0-3
7 0-7 (all) 7 0, 1 7 7 7 0-3
8 0 8 0, 1
9 0, 2, 5
10 0, 2, 5
11 0, 2, 5
12 0-3, 5, 6