User Manual
Programming Reference 4-55
H.001 Motor Nameplate Base Frequency (continued)
The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and the
setting of Torque Boost Voltage in H.003. See figure 4.10.
Figure 4.10 – Volts/Hz Ratio
30
Maximum
V/Hz
H.001
Minimum
V/Hz
Motor
Voltage,
H.000
(volts)
Output Frequency
(Hz)
100%
H.002 Motor Nameplate Amps
This parameter is the
motor amp rating as it
appears on the motor
nameplate.
Parameter Range: Power Module-dependent
Default Setting: Power Module-dependent, see Appendix C
Parameter Type: Configurable
Refer also to parameters: P.005 Current Limit
!
ATTENTION: This parameter must not exceed the rated amps found on
the motor nameplate. Excess heating of the motor could result if this is
not done. Failure to observe this precaution could result in damage to,
or destruction of, the equipment.