User Manual
4-46 LiquiFlo AC Drive, Software Reference Version 6.4
Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055.
Note that if P.000 = rE, but the REMOTE/LOCAL switch at terminal 17 is set to LOCAL
(closed), the STOP key is active even if P.055 is set to ON.
P.055 STOP/RESET Key Disable
This parameter
disables the
STOP/RESET key
except from the
selected control
source.
Parameter Range: OFF = Enable the STOP/RESET key regardless of
the control source
ON = Disable the STOP/RESET key except from the
selected control source
Default Setting: OFF
Parameter Type: Tun ab l e
Refer also to parameters: P.000 Control Source
!
ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety precaution,
Reliance Electric recommends that an emergency stop push button be
located near the drive in an easily accessible location. As a further safety
precaution, the user should post a warning on the drive to alert personnel
that the STOP/RESET key is not functional. Failure to observe this
precaution could result in severe bodily injury or loss of life.
Table 4.7 – STOP/RESET Key Status Based on P.000 and P.055
Control Source
(P.000 =) P.055
Front Panel
STOP/RESET Key
OIM/CS3000
STOP/RESET Key
Front panel (LOCL) OFF Active Active
Terminal strip (rE) OFF Active Active
Network/option port (OP) OFF Active Active
OIM/CS3000 (SErL) OFF Active Active
Front panel (LOCL) ON Active Inactive
Terminal strip (rE) ON Inactive Inactive
Network/option (OP) ON Inactive Inactive
OIM/CS3000 (SErL) ON Inactive Active