LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.
The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations: ! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product.
CONTENTS Preface ................................................................................................................................... VII Chapter 1 Starting Up the Drive for Volts/Hertz Regulation 1.1 Preparing for Start Up (Volts/Hertz)................................................................. 1-2 1.2 Start-Up Procedure (Volts/Hertz)..................................................................... 1-3 Chapter 2 Starting Up the Drive for Vector Regulation 2.
Appendix C Power Module-Dependent Parameter Default Values ............................................. C-1 Appendix D Default Parameter Settings ...................................................................................... D-1 Appendix E Configuring the Digital Inputs When the RMI Board Is Installed in the Drive ........... E-1 Appendix F Using the Terminal Strip Analog Input ..................................................................... F-1 Appendix G Drive Regulation Overview............
List of Figures Figure 3.1 – Keypad/Display..................................................................................... 3-1 Figure 3.2 – Example of a Monitor Mode Display..................................................... 3-2 Figure 3.3 – Example of a Program Mode Display ................................................... 3-4 Figure 4.1 – Parameter Menu Structure ................................................................... 4-2 Figure 4.2 – Analog Output Selection and Scaling .............
IV LiquiFlo AC Drive, Software Reference Version 6.
List of Tables Table 3.1 – Display Range Examples....................................................................... 3-5 Table 3.2 – Drive Status LEDs ................................................................................. 3-8 Table 3.3 – Monitor Mode LEDs ............................................................................... 3-9 Table 4.1 – Speed Reference Source Based on P.000 and AUTO/MAN Key Status....................................................................................
VI LiquiFlo AC Drive, Software Reference Version 6.
PREFACE This manual is a start-up and programming reference guide for the version 6.4 LiquiFlo™ drive. The drive can be set up for either volts per hertz (V/Hz) or vector regulation. This manual provides a start-up procedure for both. The start-up procedures are followed by reference information. This information includes a complete list of all parameters and a description of the keypad/display. • You will need to know how to use the keypad to perform the start-up procedures described in chapters 1 and 2.
VIII LiquiFlo AC Drive, Software Reference Version 6.
CHAPTER 1 Starting Up the Drive for Volts/Hertz Regulation This chapter describes the basic start-up procedure for drives which utilize open-loop V/Hz regulation. V/Hz regulation is the default method of regulation. You do not need to select it. If you are starting up a drive which will perform vector regulation, refer to the vector start-up procedure in chapter 2.0 instead. Do not perform the start-up procedure in this chapter.
1.1 Preparing for Start Up (Volts/Hertz) Read through the following sections to prepare for the start-up procedure. What You Need to Know: • You must be qualified to perform the procedure and be familiar with V/Hz regulation. • You should be familiar with the keypad/display. If you are not familiar with the keypad/display, refer to chapter 3, which describes it. What You Need to Do: • Complete all hardware installation as described in the hardware reference manual.
To Restore All the Default Values to General (P) Parameters: If you need to restore all the default values for General (P) parameters after programming them, you can do so using the Restore Defaults parameter (P.050). 1.2 Start-Up Procedure (Volts/Hertz) This section describes the start-up procedure for drives set up for V/Hz regulation. Before using this procedure, you should have read section 1.1 for information you need to know before working with the drive. Step 1.
Step 2. Select Program Mode In this step, you will select program mode, which will give you access to the First Menu General (P) parameters. Press the PROGRAM key. P.--RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE Password STOP RESET AUTO MAN REVERSE PROGRAM START The PROGRAM LED is on and the First Menu General (P) parameters can be accessed. ENTER RELIANCE ELECTRIC Step 3. Program First Menu General Parameters P.000 - P.
Step 3.3 Press the ENTER key to display the default setting of P.001. 20.0 RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN START This displays the default setting for acceleration time (20.0 seconds). ENTER RELIANCE ELECTRIC Step 3.4 Press the ▲ key to increase acceleration time, or the ▼ key to decrease acceleration time. The adjustment range is: 1.0 to 999.9 seconds. VALUE ENTERED: Step 3.
Step 3.7 Press the ENTER key to display the default setting of P.002. 20.0 RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN START This displays the default setting for deceleration time (20.0 seconds). ENTER RELIANCE ELECTRIC Step 3.8 Press the ▲ key to increase deceleration time, or the ▼ key to decrease deceleration time. The adjustment range is: 1.0 to 999.9 seconds. VALUE ENTERED: Step 3.
Step 3.11 Press the ENTER key to display the default setting of P.003. 5.0 RUNNING SPEED VOLTS AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG START This shows that the default setting for Minimum Speed is 5.0 Hz. ENTER RELIANCE ELECTRIC Step 3.12 Press the ▲ key to increase minimum speed or the ▼ key to decrease minimum speed. The adjustment range is: 0.5 Hz to the value set for P.004 (Maximum Speed).
Step 3.15 Press the ENTER key to display the default setting of P.004. ATTENTION:The user is responsible for ensuring that driven machinery, all drive-train mechanisms, and application material are capable of safe operation at the maximum operating speed of the drive. In V/Hz regulation, overfrequency protection in the drive is provided by means of H.022. Failure to observe this precaution could result in bodily injury. ! 60.
Step 3.18 Press the ▲ key to display P.005, Current Limit. p.005 RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN START This parameter sets Current Limit, which corresponds to the value in parameter P.095, Power Module Output Amps. ENTER RELIANCE ELECTRIC Step 3.19 Press the ENTER key to display the default setting of P.005.
Step 3.21 Press the ENTER key to save the entered value. p.005 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter number is displayed. You can now move to the next parameter. ENTER RELIANCE ELECTRIC Step 4. Enter the Second Menu Password This step is required in order to access the Second Menu General (P) parameters and the Volts/Hertz (H) parameters. Step 4.
Step 4.3 Press the ▲ key until the password number 107 is displayed. i07 RUNNING SPEED VOLTS AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG START Note that the password, and access to the Second Menu, will be retained if the drive loses and regains power. ENTER RELIANCE ELECTRIC Step 4.4 Press the ENTER key to save the password number. p.
Step 5.2 Press the ▲ key twice. E SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET The error log (Err) is bypassed, then..... RUNNING AMPS Hz Kw TORQUE Password STOP RESET Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START h.--SPEED VOLTS AUTO MAN RUNNING ENTER RELIANCE ELECTRIC ...the Volts/Hertz (H) parameter main menu is displayed. AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 5.
Step 5.5 If no change was made, press the ENTER key to return to the parameter. If you changed the value, press ENTER to accept the change and return to the parameter. h.000 RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter. ENTER RELIANCE ELECTRIC Step 5.6 Press the ▲ key to display H.
Step 5.8 Press the ▼ key to decrease base frequency, if necessary. This value will typically not need to be changed from 60 Hz. Step 5.9 Press the ENTER key. h.00i RUNNING SPEED VOLTS AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz Kw TORQUE Password STOP RESET AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter. ENTER RELIANCE ELECTRIC Step 5.10 Press the ▲ key to display H.002, Motor Nameplate Amps.
Step 5.12 Press the ▲ key to increase the motor nameplate amps, or the ▼ key to decrease motor nameplate amps. The adjustment range depends on the drive rating. See Appendix C. VALUE ENTERED: Step 5.13 Press the ENTER key to save the changed value. h.002 RUNNING SPEED VOLTS Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter.
Step 5.16 Press the ▲ key to increase the torque boost voltage, or the ▼ key to decrease torque boost voltage. Important: If you set H.003 = 0, you must perform the identification test, controlled by H.020, prior to running. Refer to the H.020 parameter description for more information. The adjustment range is: 0.0% to 20.0% VALUE ENTERED: Step 5.17 Press the ENTER key to save the changed value. h.
Step 5.19 Press the ENTER key. 0 RUNNING SPEED VOLTS The default setting is 0. AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET START ENTER RELIANCE ELECTRIC Step 5.20 Press the ▲ key to increase the selection value, or leave it at 0. If you do not have AC input or you are using a snubber resistor, see the H.017 parameter description for more informaton.
Step 5.22 Press the ▲ key until H.018, Volts/Hertz Curve Type, is displayed. h.0i8 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This parameter selects the type of curve for volt/hertz regulation. See chapter 4 and step 5.24 for more information. ENTER RELIANCE ELECTRIC Step 5.23 Press the ENTER key.
Step 6. Return to Monitor Mode This step describes how to exit program mode and return to monitor mode. Step 6.1 The display should now show the last parameter adjusted in step 5, H.018. h.0i8 RUNNING SPEED VOLTS AMPS Hz Kw AUTO FORWARD TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG START ENTER RELIANCE ELECTRIC Step 6.2 Press the PROGRAM key twice to exit program mode.
ATTENTION:The subsequent steps require rotating parts and/or electrical circuits to be exposed. Stay clear if unit must be running, or disconnect and lock out or tag power source if contact must be made. Failure to observe this precaution could result in severe bodily injury or loss of life. ! Important: The stop input on the terminal strip is not active when the Control Source parameter (P.000) is set to LOCL, as it is during this start-up procedure. Use the STOP/RESET key if you need to stop the drive.
Step 7.5 Press the ▼ key to decrease the speed reference value. Step 7.6 Press the ENTER key to return to monitor mode. 0 RUNNING SPEED VOLTS AMPS Hz AUTO FORWARD Kw TORQUE Forward Reverse PROGRAM RUN JOG REVERSE PROGRAM Password STOP RESET AUTO MAN REMOTE JOG START ENTER RELIANCE ELECTRIC Step 7.7 Verify that you have selected RUN and FORWARD. Press the START key.
Step 7.9 • If the rotation direction is NOT correct, press the STOP/RESET key and continue with step 7.10. • If the rotation direction is correct, continue with step 7.14. 0 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START When the STOP/RESET key is pressed, the RUNNING LED turns off. ENTER RELIANCE ELECTRIC Step 7.10 Turn off and lock out or tag power to the drive. Step 7.
Step 8. Run the Drive This step describes how to adjust the speed reference from the keypad and run the motor up to maximum speed in Hz. At maximum Hz, you must check values in monitor mode. This step assumes you have connected the motor to the load and turned power back on. ATTENTION: The user is responsible for ensuring that driven machinery, all drive-train mechanisms, and application material are capable of safe operation at the maximum operating speed of the drive.
Step 8.3 Press the ENTER key repeatedly to move to the VOLTS display. 460 RUNNING SPEED VOLTS AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz Kw TORQUE Password STOP RESET AUTO FORWARD REVERSE PROGRAM START This example shows the output volts at Maximum Speed (P.004). Your actual reading may be different. ENTER RELIANCE ELECTRIC VALUE READ: Step 8.4 Press the ENTER key to move to the AMPS display. 3.
CHAPTER 2 Starting Up the Drive for Vector Regulation This chapter describes the basic start-up procedure for drives which utilize flux vector control (FVC) or sensorless vector control (SVC). Part of this procedure describes how to select vector regulation. If you are starting up a drive which will perform V/Hz regulation, refer to the V/Hz start-up procedure in chapter 1.0 instead. Do not perform the start-up procedure in this chapter.
2.1 Preparing for Start Up (Vector) Read through the following sections to prepare for the start-up procedure. What You Need to Know: • You must be qualified to perform the procedure and be familiar with vector regulation. • You should be familiar with the keypad/display. If you are not familiar with the keypad/display, refer to chapter 3, which describes it. What You Need to Do: • Complete all hardware installation as described in the hardware reference manual.
To Restore a Default Parameter Value after Writing over It: If you enter the wrong value while programming parameters, you can restore the default if you have not yet pressed the ENTER key. To do so: 1. Press the PROGRAM key. 2. Press the ENTER key. The default value of the parameter will be displayed again. You can select it with ENTER or enter a new one and press ENTER.
Step 2. Select Program Mode In this step, you will select program mode, which gives you access to the First Menu General (P) parameters. Step 2.1 Press the PROGRAM key. P.--SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START The PROGRAM LED is on and the First Menu General (P) parameters can be accessed. ENTER RELIANCE ELECTRIC Step 2.2 Press the ENTER key. p.
Step 3.2 Press the ENTER key. 0 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING Zero is displayed. AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 3.3 Press the ▲ key until the password 107 is displayed.
Step 4. Program the Drive for Vector Regulation This step describes how to change parameter P.048 (Volts/Hertz or Vector Regulation) to vector. Within vector regulation, you can program the drive for flux vector control (FVC) or sensorless vector control (SVC). FVC operation requires an encoder. SVC operation does not require an encoder. Both options require U.048 to be set to UEC. In a later step, you will select either the FVC option or the SVC option. When you enter the value for vector regulation (P.
Step 4.4 Press the ENTER key to save the setting. p.048 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter number is displayed. You can now go to the next step. ENTER RELIANCE ELECTRIC Step 4.5 Note the display.
Step 5. Program First Menu General Parameters P.000 - P.005 This step describes how to change First Menu General (P) parameters P.000 through P.005. P.000 selects where the drive is controlled from. This procedure assumes local control from the keypad (P.000 = LOCL), which is the default setting for the parameter. Step 5.1 Press the PROGRAM key. P.
Step 5.4 Press the ENTER key to display the default setting of P.001. 20.0 RUNNING SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This displays the default setting for acceleration time (20.0 seconds). ENTER RELIANCE ELECTRIC Step 5.5 Press the ▲ key to increase acceleration time, or the ▼ key to decrease acceleration time. The adjustment range is: 0.1 to 999.9 seconds. VALUE ENTERED: Step 5.
Step 5.8. Press the ENTER key to display the default setting of P.002. 20.0 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This displays the default setting for deceleration time (20.0 seconds). ENTER RELIANCE ELECTRIC Step 5.9 Press the ▲ key to increase deceleration time, or the ▼ key to decrease deceleration time. The adjustment range is: 0.1 to 999.9 seconds. VALUE ENTERED: Step 5.
Step 5.11 Press the ▲ key to display P.003, Minimum Speed. ATTENTION: The drive can operate at and maintain zero speed. The user is responsible for ensuring safe conditions for operating personnel by providing suitable guards, audible or visual alarms, or other devices to indicate that the drive is operating or may operate at or near zero speed. Failure to observe this precaution could result in severe bodily injury or loss of life. ! p.
Step 5.14 Press the ENTER key to save the changed value. p.003 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter number is displayed. You can now go to the next parameter. ENTER RELIANCE ELECTRIC Step 5.15 Press the ▲ key to display P.004, Maximum Speed.
Step 5.17 Press the ▲ key to increase maximum speed or the ▼ key to decrease maximum speed. The adjustment range is: 10 to Motor Top Speed (set in parameter U.017). Refer to Step 7 for parameter U.017. VALUE ENTERED: Step 5.18 Press the ENTER key to save the changed value. p.004 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter number is displayed.
Step 5.21 Press the ▼ key to decrease current limit percent. Note that changing current limit rating affects the maximum attainable torque the motor can produce. The adjustment range for current limit is: U.006 (Magnetizing Current) to 150%. VALUE ENTERED: Step 5.22 Press the ENTER key to save the entered value. p.
Step 6.2 Press the ▲ key twice. E SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET The error log (Err) is bypassed, then..... RUNNING AUTO FORWARD REVERSE PROGRAM START u.--SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG RUNNING ENTER RELIANCE ELECTRIC AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ...the Vector (U) parameter main menu is displayed. ENTER RELIANCE ELECTRIC Step 6.
Step 6.5 Press the ▲ key to increase the value. Important: If you are going to change the value for this parameter, see the description in chapter 4. The adjustment options are: 0 = Speed loop output (default setting) 1 = Terminal strip analog input 2 = Option port (network torque reference register) 3 = Selected speed reference VALUE ENTERED: Step 6.6 Press the ENTER key to save the displayed value. u.
Step 6.8 Press the ENTER key to display the default setting of U.001. ! ATTENTION: Do not use a 4096 PPR encoder with a 2-pole motor. Overspeed and motor damage can result. Failure to observe this precaution could result in bodily injury. i024 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This displays the default setting for Encoder PPR, 1024 PPR. ENTER RELIANCE ELECTRIC Step. 6.
Step 6.11 Press the ▲ key to display U.002, Motor Poles. ! ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002 (Motor Poles), U.003 (Motor Nameplate Base Frequency), U.005 (Motor Nameplate RPM), and U.017 (Motor Top Speed) determines the motor maximum speed. These parameters must be set by a qualified person who understands the significance of setting them accurately. Failure to observe this precaution could result in bodily injury. u.
Step 6.14 Press the ENTER key to save the changed value. u.002 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter. ENTER RELIANCE ELECTRIC Step 6.15 Press the ▲ key to display U.003, Motor Nameplate Base Frequency. ! ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002 (Motor Poles), U.
Step. 6.17 Press the ▲ key to increase the motor nameplate base frequency or the ▼ key to decrease motor nameplate base frequency. The adjustment range is: 15.0 Hz to 120.0 Hz VALUE ENTERED: Step 6.18 Press the ENTER key to save the changed value. u.003 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter.
Step 6.20 Press the ENTER key to display the default setting of U.004. 7.i RUNNING SPEED VOLTS AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG START This displays the Motor Nameplate Amps setting. The default depends on the HP rating of the Power Module. The display shown here is only an example. ENTER RELIANCE ELECTRIC Step 6.
Step 6.23 Press the ▲ key to display U.005, Motor Nameplate RPM. ! ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002 (Motor Poles), U.003 (Motor Nameplate Base Frequency), U.005 (Motor Nameplate RPM), and U.017 (Motor Top Speed) determines the motor maximum speed. These parameters must be set by a qualified person who understands the significance of setting them accurately. Failure to observe this precaution could result in bodily injury. u.
Step 6.26 Press the ENTER key to save the changed value. u.005 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter is displayed. You can now move to the next parameter. ENTER RELIANCE ELECTRIC Step 6.27 Press the ▲ key to display U.006, Motor Magnetizing Current.
Step 6.29 Press the ENTER key to display the default setting of U.007. 460 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This displays the default setting for the Motor Nameplate Volts. The default setting depends on the Power Module rating and is factory set. The display shown here is only an example. ENTER RELIANCE ELECTRIC Step 6.
6.33 Press the ENTER key to display the default setting of U.022. 5.0 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This displays the default setting for Motor Nameplate Horsepower. The default setting depends on the Power Module rating and is factory-set. The display here is only an example. ENTER RELIANCE ELECTRIC 6.
Step 7. Set the Motor Top Speed This step sets the Motor Top Speed (U.017) in RPM. For applications that do not support field weakening, Motor Top Speed must be equal to U.005 (Motor Nameplate RPM). For applications that do support field weakening, Motor Top Speed is the maximum field-weakened speed. Step 7.1 Press the ▼ key until U.017 is displayed. u.
Step 7.4 Press the ENTER key to save the displayed value. u.0i7 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START After pressing ENTER, the same parameter number is displayed. You can now go to the next step. ENTER RELIANCE ELECTRIC Step 8.
What Happens if a Fault Occurs During Self-Tuning? 1. If the drive stops due to a fault, the motor will coast to stop. A self-tuning fault code (SF) will be displayed and must be cleared. Refer to chapter 5 for more information. 2. Once the drive is stopped, parameter U.008 will be reset to OFF and the self-tuning procedure will be completed. The results are stored in U.009, Torque Self-Tune Result. Step 8.1 Press the ▼ key to display U.008, Torque Self-Tune Enable. u.008 RUNNING SPEED VOLTS Parameter U.
Step 8.4 Press the ENTER key. u.008 RUNNING SPEED VOLTS AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE REVERSE PROGRAM Password STOP RESET START After pressing ENTER, the same parameter is displayed. You can now go to the next step. ENTER RELIANCE ELECTRIC Step 8.5 Press the PROGRAM key twice to exit program mode.
Step 8.7 Self-tuning is now completed. If a zero is displayed, the self-tuning procedure was completed successfully. Go to step 10. If SF is displayed, the procedure was not successfully completed. Go to step 9 to view parameter U.009 for the specific fault code. 0 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING When self-tuning is complete, the motor will ramp to a stop.
Step 9.3. Press the ▲ key until U.009 is displayed. u.009 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 9.4 Press the ENTER key to view the test result. Step 9.5 Refer to the U.009 parameter description in chapter 4 for the corresponding cause and corrective action. Step. 9.6 Once the cause of the fault has been corrected, repeat the self-tuning procedure (step 8).
Step 10.2 Verify that the AUTO LED is off (press the AUTO/MAN key until the AUTO LED turns off). This selects the local keypad as the speed reference source. Step 10.3 Press the ▲ key or the ▼ key once. i50 RUNNING SPEED VOLTS AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz Kw TORQUE Password STOP RESET AUTO FORWARD REVERSE PROGRAM START The monitor mode LEDs will all turn off and the manual speed reference value will be displayed.
Step 10.8 Visually check that the motor rotates counter-clockwise (CCW) when viewed from the driven motor shaft end. CCW Step 10.9 • If the rotation direction is NOT correct, press the STOP/RESET key and continue with step 10.10. • If the rotation direction is correct, continue with step 10.14.
Step 11. Run the Drive This step describes how to increase the speed reference across the speed range and check for proper motor operation. This step assumes that P.000 is set to LOCL (control is local) and the motor is connected to the load and power is turned back on. Step 11.1 Press the START key.
Step 11.3 Press the ENTER key to move to the VOLTS display. 460 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START This sample display shows the output volts at maximum speed. Your actual reading may be different. ENTER VALUE READ: RELIANCE ELECTRIC Step 11.4 Press the ENTER key to move to the AMPS display. 2.
Step 12. Tune the Speed Regulator Tuning the speed regulator consists of adjusting the speed regulator proportional and integral gain values according to the application. The speed regulator uses these values to calculate the drive’s response to a change in speed reference and to changes in load or other factors in the driven system. This procedure may or may not be required. This step assumes you have connected the motor to the load. Step 12.1 Press the START key.
Step 12.4 Press the ▲ key until U.012 is displayed. This parameter sets the speed regulator proportional gain. u.0i2 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC The speed loop gain is set for typical speed loop response and should be adjusted only when faster speed loop response is required.
2-38 LiquiFlo AC Drive, Software Reference Version 6.
CHAPTER 3 Using the Keypad/Display to Program, Monitor, and Control the Drive The front-panel keypad/display is used to program, monitor, and control the drive. It operates in two modes, monitor mode and program mode. The functions available at the keypad depend on what mode the keypad/display is in and what is selected as the drive control source. In monitor mode (the default mode), you can monitor specific drive outputs as well as enter the speed or frequency reference for the drive.
3.1 Monitor Mode Monitor mode is the keypad/display’s default mode during drive operation or it is entered by pressing the PROGRAM key until the PROGRAM LED turns off. The following output data can be displayed in monitor mode: • Speed • Volts • Amps • Hz • Kw • Torque (vector regulation only) • Selected reference (speed or torque) To select a value to monitor, press the ENTER key until the LED turns on next to the desired display item. Pressing the ENTER key advances you through each of the displays.
Step 2. Press the ENTER key repeatedly to advance through each of the monitor mode LEDs. All of the monitor mode LEDs will then turn on at once and the reference will be displayed. Note that the displayed speed reference value is scaled based on P.028. The torque reference value is displayed in percent. If the selected reference is negative and its value is greater than 999, the SPEED LED will flash (refer to section 3.4.1, Display Range).
Display shows menu selections: P.--H.--- (If P.048 = U-H) U.--- (If P.048 = UEC) r.--- (if the optional RMI board is installed) or Err (Error Log) p.--SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC PROGRAM LED is on Figure 3.3 – Example of a Program Mode Display 3.
Table 3.1 – Display Range Examples Example If the actual number is... It will appear on the display as... And the SPEED LED will... A 1000.5 1000. Not flash B -999 -999 Not flash C -1000 1000 Flash D -99.9 -99.9 Not flash E -1000.5 1000. Flash F -9.99 -9.99 Not flash G -100.25 100.2 Flash H -9.999 9.999 Flash This does not apply for the speed display. For the speed display, the FORWARD or REVERSE LEDs indicate actual speed reference polarity. 3.4.
3.5 The Keypad The drive’s keypad has nine membrane keys that are used to monitor, program, and control the drive. Use the AUTO/MAN key to switch between the auto speed reference and the manual speed reference as shown below. AUTO/MAN Status Control Source (P.000) Speed Reference Source AUTO selected Local keypad/display (P.000=LOCL) Terminal strip Terminal strip remote inputs (P.000=rE) Terminal strip Option port (P.000=OP) Network Serial port (P.
Use the ▲ and ▼ keys to: • Step through the drive parameter menus and error log when the keypad/display is in program mode • Increase (or decrease) a numeric value (such as the reference or a parameter value) Hold down these keys to increase the scroll speed.
3.6 Drive Status LEDs The keypad contains eight LEDs that show the present drive status. Table 3.2 describes what each drive status LED means. Table 3.2 – Drive Status LEDs LED RUNNING REMOTE JOG AUTO FORWARD1 REVERSE1 PROGRAM PASSWORD Status Meaning On Output power is being applied to the motor. Off Output power is not being applied to the motor. On The drive is being controlled (START, RUN/JOG, FORWARD/REVERSE, speed reference) from a source other than the keypad.
3.7 Monitor Mode LEDs Table 3.3 describes the values that will be displayed when the corresponding monitor mode LED is on. Table 3.3 – Monitor Mode LEDs Monitor Mode LED Corresponding Display When LED Is On (Actual Values) SPEED Motor speed is displayed. This value is scaled in parameter P.028. VOLTS Drive output volts are displayed. This value is not DC bus volts. AMPS Drive output amps are displayed. Hz Drive output frequency in hertz is displayed.
3-10 LiquiFlo AC Drive, Software Reference Version 6.
CHAPTER 4 Programming Reference To program the drive for a specific application, you display the appropriate parameter and adjust it as required. The parameters are used to define characteristics of the drive. This chapter provides an overview of the parameter menus as well as detailed descriptions of each parameter. This chapter also describes how to access, display, and modify parameters. 4.
First Menu General Parameters P.000 - P.006 Enter password into P.006 Second Menu General Parameters P.007 - P.099 P.048 = U-H (default) P.048 = UEC Volts/Hertz Parameters H.000 - H.022 Vector Parameters U.000 - U.048 If optional RMI board is installed RMI Parameters r.001 - r.066 Error Log Password must be entered into P.006 to access these parameters Figure 4.1 – Parameter Menu Structure 4.
Parameter Name: the name assigned to a parameter number. The parameter name is not displayed when programming the drive using the keypad/display. The parameter name is only visible when using the CS3000 software or Operator Interface Module (OIM). Parameter Description: a description of the parameter’s function. Parameter Range: the pre-defined parameter value limits or selections. Default Setting: the factory default setting.
Step 3. Once the desired menu is displayed, press the ENTER key to select it. p.000 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START The first parameter number in the menu or the last parameter number previously accessed from that menu will be displayed. ENTER RELIANCE ELECTRIC Step 4. Press the ▲ key or the ▼ key to move through the parameters. p.
Step 7. Press the ENTER key to save the changed value. - OR Press the PROGRAM key to exit the parameter without changing the value. p.00i SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER The parameter number will be displayed again. Important: The value will not be written into memory unless the ENTER key is pressed.
To prevent unauthorized password use, a zero value (not the saved password value) is displayed whenever this parameter is accessed. Note that parameter values and the local keypad status are retained through a line dip or power shutdown. 4.5 First Menu Parameters The First Menu contains General parameters that are most commonly used for simple applications. No password is required to access them. These parameters apply to both vector and V/Hz programming and are described in detail in section 4.5.1. 4.5.
P.000 Control Source (continued) Table 4.1 – Speed Reference Source Based on P.000 and AUTO/MAN Key Status Control Source (P.000) AUTO/MAN Status Speed Reference Source Local keypad/display (P.000=LOCL) AUTO selected Terminal strip MAN selected Local keypad/display or OIM Terminal strip remote inputs (P.000=rE) AUTO selected Terminal strip MAN selected Local keypad/display or OIM Option port (P.
P.001 Accel Time 1 (RAMP 1) (continued) If the motor load inertia is high, or the Current Limit (P.005) setting is too low, actual motor acceleration time will be longer than the time set in P.001. If Accel Time 1 is set too short, an overcurrent fault may occur. P.002 Decel Time 1 (RAMP 1) For V/Hz regulation, this parameter specifies the amount of time in which the motor ramps from Maximum Speed (P.004) to zero speed.
P.003 Minimum Speed This parameter limits the speed reference to the drive. Regardless of what speed reference is supplied, the regulator will not command a speed less than the value in P.003. Parameter Range: 0.5 to P.004 Maximum Speed (V/Hz) 0 to P.004 Maximum Speed (vector) Default Setting: 5.0 Hz (V/Hz) 150 RPM (vector) Parameter Type: Tunable Refer also to parameters: P.004 Maximum Speed ! ATTENTION: The drive can operate at and maintain zero speed.
P.005 Current Limit This parameter provides the means to limit motor stator current while running at constant speed or during acceleration. Parameter Range: 50 to 110% (V/Hz) U.006 to 150% (vector) Default Setting: 100% (V/Hz) 150% (vector) Parameter Type: Tunable Refer also to parameters: P.095 Power Module Output Amps H.002 Motor Nameplate Amps U.004 Motor Nameplate Amps U.
4.6 Second Menu Parameters The Second Menu contains parameters used for more complex applications. Within the Second Menu are General (P.---) parameters that apply to both vector and V/Hz programming, and Vector (U.---) or Volts/Hertz (H.---) parameters. If an optional RMI board is installed in the drive, RMI (r.---) parameters are also contained in the Second Menu.
Step 2. Press the ENTER key. P.000 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 3. Press the ▲ displayed. p.006 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING key to increment the parameter numbers until P.
Step 6. Press the ENTER key to select the password. p.006 RUNNING SPEED VOLTS AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AMPS Hz AUTO FORWARD Kw TORQUE Password STOP RESET P.006 is displayed. REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 7. Press the ▲ key to verify the access status. p.
4.6.2 Second Menu General Parameter Descriptions (P.007 to P.099) P.007 Terminal Strip Digital Inputs Configure The LiquiFlo drive provides multiple configurations of digital inputs 6, 7, and 8 on the terminal strip. This parameter determines how these inputs are used. The P.008 (Terminal Strip Speed Reference Source) selection will limit the selection of P.007 because the P.008 selection may use one or more of digital inputs 6 through 8.
P.007 Terminal Strip Digital Inputs Configure (continued) FWD/REV FWD/REV allows you to select between forward or reverse operation. If the input is closed, this function will invert the selected speed reference. For example, if the selected speed reference value is negative (<0) and the FWD/REV input is closed, the resulting speed reference will be positive. The digital input for FWD/REV is active only if the control source is remote.
P.007 Terminal Strip Digital Inputs Configure (continued) TRQ/SPD TRQ/SPD allows you to switch between torque regulation and speed regulation while the drive is running or stopped. This feature only applies when the drive has been configured as a vector regulator (P.048 = UEC), and U.000 (Torque Reference Source) > 0. To provide smooth transitioning when switching from torque to speed, the speed regulator is preset with the last torque reference.
P.008 Terminal Strip Speed Reference Source This parameter selects the source of the terminal strip speed reference. Parameter Range: 0 = Analog reference. (Digital inputs 6, 7, and 8 are not used. See P.007.) 1 = MOP selection. (Uses terminal strip digital input 6 for MOP increment and digital input 7 for the MOP decrement function. Digital input 8 is not used.) The terminal strip speed reference is used when: 2 = Two (2) preset speeds. (Uses terminal strip digital input 6.
P.008 Terminal Strip Speed Reference Source (continued) Table 4.3 – Acceptable P.007 and P.008 Selection Combinations P.007 Selections 0 1 2 3 4 5 6 7 8 9 10 11 12 0 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 1 2 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ P.008 Selections 3 4 ✔ ✔ ✔ ✔ ✔ ✔ 5 6 7 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ = Selection combination is acceptable. P.007/P.008 Selection Example If you want to select the MOP as the speed reference source, P.008 must be set to 1. Next, select the value for P.
P.010 Terminal Strip Analog Input Gain This parameter is used to compensate for component tolerance errors or insufficient voltage from the input reference source at the terminal strip. Parameter Range: 0.100 to 5.000 Default Setting: 1.000 Parameter Type: Tunable Refer also to parameters: P.000 Control Source This parameter is not used if the terminal strip analog input is used as vector torque reference (U.000 = 1). For more information about the analog input, refer to Appendix F. P.
P.011 Terminal Strip Analog Input Configure (continued) ! ATTENTION: The drive may inadvertently start due to the effects of temperature or electrical noise on the analog input when the analog input is configured to start and stop the drive (P.011 = 12), and the following conditions are true: • P.000 = rE • The function loss, stop, and start inputs on the terminal strip are all closed.
. P.012 Terminal Strip Analog Output Source This parameter selects the source of the analog output signal. Parameter Range: 0 = Speed (bipolar) 1 = Torque (bipolar) 2 = Speed (unipolar) 3 = Current (unipolar) (V/Hz) Torque (unipolar) (vector) Default Setting: 0 Parameter Type: Tunable Refer also to parameters: N/A Selections 2 and 3 select the same signals as selections 0 and 1, but instead of providing a 5V (1/2 scale) offset to allow for a bipolar signal, no 5V offset is used.
P.013 Output Relay Configuration This parameter specifies the type of status indication provided by the output relay contacts (terminals 28, 29, 30, and 31 on the drive’s terminal strip). Parameter Range: 0 = Output relay is energized to show state of active fault (IET). 1 = Output relay is energized to show state of drive running with 0.5 second delay added between a start assertion and generation of motor voltage. 2 = Output relay is energized to show state of drive running but without 0.
P.000 Selected Speed Ref P.014 0 1 2 3 4 5 6 7 8 9 None Terminal Strip Analog Input Option Port Max Speed RMI Speed Control Loop Torque Controller x P.015 100 Selected Trim Ref Torque Feedback Figure 4.3 – Trim Reference Source Selection P.015 Trim Gain Percentage This parameter specifies a percentage of the selected trim reference entering the speed regulator. Parameter Range: -100.0 to +100.0% (1.0 = 1%) Default Setting: 0.0 Parameter Type: Tunable Refer also to parameters: P.
P.016 Draw Gain Percentage This parameter is used to increase or decrease the selected speed reference to the speed regulator. Parameter Range: -100.0 to +100.0% (1.0 = 1%) Default Setting: 0.0 Parameter Type: Tunable Refer also to parameters: N/A This parameter allows multiple drive sections with a common line reference, but with different values for draw gain, to run at different speeds depending on the percent draw. P.
P.018 Decel Time 2 (RAMP 2) This parameter specifies the deceleration time when a second ramp selection is configured as a digital input. Parameter Range: 1.0 to 999.9 seconds (V/Hz) 0.1 to 999.9 seconds (vector) Default Setting: 20.0 Parameter Type: Tunable Refer also to parameters: P.002 Decel Time 1 P.007 Terminal Strip Digital Inputs Configure When the RAMP 2 deceleration time digital input is asserted, the RAMP 2 acceleration time also takes effect.
The acceleration and deceleration times must be set the same for the S-Curve ramp to function the same for acceleration as for deceleration. If the deceleration time is set lower than the acceleration time, the deceleration time specified may not be met. P.004 (V/Hz) U.017 (Vector) 20% 20% t t accel time decel time S-Curve Acceleration S-Curve Deceleration Figure 4.5 – S-Curves P.020 Jog Speed Reference This parameter is the speed reference for the drive when JOG is selected.
. P.021 Jog Ramp Accel Time For V/Hz regulation, this parameter specifies the amount of time it takes the motor to ramp from zero speed to Maximum Speed (P.004) when JOG is selected. Parameter Range: 1.0 to 999.9 seconds (V/Hz) 0.1 to 999.9 seconds (vector) Default Setting: 20.0 Parameter Type: Tunable Refer also to parameters: P.004 Maximum Speed U.
P.023 MOP Accel/Decel Time For V/Hz regulation, this parameter specifies the amount of time it takes the MOP to ramp from Maximum Speed (P.004) to zero speed and from zero speed to Maximum Speed (P.004). Parameter Range: 0.1 to 999.9 seconds Default Setting: 20.0 Parameter Type: Tunable Refer also to parameters: P.004 Maximum Speed P.007 Terminal Strip Digital Inputs Configure P.008 Terminal Strip Speed Reference Source U.
P.025 Stop Type This parameter selects how the motor will stop when a stop command is given. Parameter Range: 0 = Coast-to-rest stop 1 = Ramp stop Default Setting: 0 Parameter Type: Tunable Refer also to parameters: P.002 Decel Time 1 P.018 Decel Time 2 P.022 Jog Ramp Decel Time U.000 Torque Reference Source ! ATTENTION: The user must provide an external, hardwired emergency stop circuit outside the drive circuitry. This circuit must disable the system in case of improper operation.
• If P.025 = 1, pressing the STOP/RESET key or giving an external stop command will cause the motor to ramp to rest within a time equal to or greater than the preset deceleration time (P.022). P.026 Function Loss Response This parameter specifies how the drive will respond to an open circuit between terminal strip inputs 16 and 20. Parameter Range: 0 = Generate a fault (IET) and coast to rest 1 = Coast to rest without a fault Default Setting: 0 Parameter Type: Tunable Refer also to parameters: P.
P.028 Speed Display Scaling This parameter defines the scaling value applied to the manual reference, the selected speed reference, and the output speed displays. Parameter Range: 10 to 9999 Default Setting: Synchronous speed based on H.001 (assuming a 4-pole motor) (V/Hz) U.017 (vector) Parameter Type: Tunable Refer also to parameters: U.017 Motor Top Speed H.001 Motor Nameplate Base Frequency For vector regulation, P.028 will correspond to U.017: Actual Speed in RPM x P.
For V/Hz regulation: Minimum reference = P.003 x P.028 H.001 Maximum reference = P.004 x P.028 H.001 V/Hz Speed Display Scaling Example Your application requires the display to be scaled to show the speed reference or the output speed as 800 gallons/minute when operating at maximum speed. H.001 (Motor Nameplate Base Frequency) = 60 Step 1. Set parameter P.028 = 800 Step 2. Enter SPEED monitor mode by pressing the PROGRAM key until the PROGRAM LED turns off and the SPEED LED turns on. Step 3.
P.031 to P.038 Preset Speed 1 through Preset Speed 8 These parameters allow the setting of up to eight different preset speeds. Parameter Range: Minimum Speed (P.003) to Maximum Speed (P.004) Default Setting: 5.0 Hz (V/Hz) 150 RPM (vector) Parameter Type: Tunable Refer also to parameters: P.007 Terminal Strip Digital Inputs Configure P.008 Terminal Strip Speed Reference Source The presets are configured using parameters P.007 and P.008. P.008 must be set to values of 2 through 7 for preset speeds.
P.031 to P.038 Preset Speed 1 through Preset Speed 8 (continued) P.038 P.037 P.036 P.035 P.034 P.033 P.032 P.031 Preset 1 (or TS Analog in) Closed Run and Start Digital In 6 (Term. 19) Closed Closed Closed Closed Digital In 7 (Term. 18) Closed Closed Closed Digital In 8 (Term. 17) Figure 4.6 – Typical Preset Operation P.039 Encoder Loss Enable This parameter enables the encoder loss detection diagnostic.
P.040 Motor Overload Enable This parameter enables the electronic motor thermal overload function. This function operates similarly to a motor overload relay to protect the motor from overheating. Parameter Range: OFF = Disable electronic motor thermal overload function ON = Enable motor thermal overload function Default Setting: ON Parameter Type: Configurable Refer also to parameters: P.041 Motor Overload Type H.002 Motor Nameplate Amps U.004 Motor Nameplate Amps P.
P.042 Line Dip Ride-Through Time For V/Hz regulation, this parameter sets the maximum time allowed for the drive to stay active during low line voltage or line voltage loss. Parameter Range: 0.1 to 999.9 seconds (V/Hz) 500 ms (vector) Default Setting: 5.0 Parameter Type: Configurable Refer also to parameters: H.017 Input Power/Snubber Configuration H.021 AC Line Voltage U.018 AC LIne Voltage For vector regulation, this value is fixed at 500 ms.
P.043 Fault Auto Reset Attempts (continued) Table 4.5 lists the faults that can be auto reset: Table 4.5 – Faults That Can Be Auto Reset Fault Code Description AIn 4 to 20 mA analog input signal loss bYC DC bus charging bypass contactor EC Earth current failure (ground fault) HIL High line voltage HU High DC bus voltage LU Low DC bus voltage nCL Network communications loss OH Drive overtemperature UbS Asymmetrical bus charge All other faults cannot be auto reset.
P.045 Output Phase Loss Enable This parameter is used to enable the output phase loss detection diagnostic. Parameter Range: OFF = Disable output phase loss diagnostic ON = Enable output phase loss diagnostic Default Setting: ON Parameter Type: Tunable Refer also to parameters: N/A This diagnostic detects phase loss between the drive and the motor. When the diagnostic is enabled and output phase loss is detected, a drive fault is logged (OPL is displayed).
. P.048 Volts/Hertz or Vector Regulation This parameter selects the drive regulator type: volts/hertz (V/Hz) or vector. Parameter Range: U-H = V/Hz control UEC = vector control Default Setting: U-H Parameter Type: Configurable Refer also to parameters: U.001 Encoder PPR For V/Hz control, the drive provides open-loop volts per hertz regulation which is appropriate for general purpose applications.
P.050 Restore Defaults This parameter resets all First and Second Menu General parameters (P.---) to factory default settings. Parameter Range: OFF = No action ON = Reset parameters to default settings Default Setting: OFF Parameter Type: Configurable Refer also to parameters: P.049 Country Defaults Note that P.048 (Volts/Hertz or Vector Regulation) is not restored to its factory default setting when P.050 is set to ON. P.
P.052 AUTO/MAN Key Disable This parameter disables the AUTO/MAN key except from the selected control source. Parameter Range: OFF = Enable the AUTO/MAN key regardless of control source ON = Disable the AUTO/MAN key except from the selected control source Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.000 Control Source P.053 Manual Reference Preset Enable When this parameter is set to ON, the AUTO/MAN key is functional only from the selected control source.
P.053 Manual Reference Preset Enable When ON is selected, the manual reference will be preset with the auto reference value when the transition is made from AUTO to MANUAL. Parameter Range: OFF = Do not preset the manual reference ON = Preset the manual reference with the auto reference at the transition from AUTO to MANUAL Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.027 Forward/Reverse Configuration P.
P.054 Level Sense Start Enable This parameter selects whether the start input is edge-sensitive or level-sensitive for remote (P.000 = rE) and option port (P.000 = OP) control sources. Parameter Range: OFF = Start input is edge-sensitive ON = Start input is level-sensitive Default Setting: OFF Parameter Type: Configurable Refer also to parameters: P.
P.054 Level Sense Start Enable (continued) Figure 4.7 shows the start, stop, and running status of the drive when configured for edge control versus level control. START STOP RUNNING Edge-Sensitive Start START STOP RUNNING Level-Sensitive Start Figure 4.7 – Drive Start, Stop, and Running Status when Configured for Edge Control vs. Level Control Note that when operating from the terminal strip (rE) or a network option, an edge is required at the start input for the following two conditions, even if P.
P.054 Level Sense Start Enable (continued) ! ATTENTION: As a safety precaution, Reliance Electric recommends that you provide an audible or visual alarm to indicate that this feature is enabled and the motor can start when power is applied to the drive. You should also post warnings on the motor, the drive, and any other applicable equipment to alert personnel that the application uses an automatic start-up feature. Failure to observe this precaution could result in severe bodily injury or loss of life.
P.055 STOP/RESET Key Disable This parameter disables the STOP/RESET key except from the selected control source. Parameter Range: OFF = Enable the STOP/RESET key regardless of the control source ON = Disable the STOP/RESET key except from the selected control source Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.000 Control Source ! ATTENTION: When P.055 is set to ON, the STOP/RESET key is functional only from the selected control source.
P.060 Network Drop Number This parameter specifies the base drop number or node number to the drive Parameter Range: Network-dependent Default Setting: 1 Parameter Type: Configurable Refer also to parameters: P.061 Network Connection Type This parameter must be set at the drive via the keypad/display or via a personal computer serial interface. This parameter cannot be written to the drive by the network master.
. P.062 Option Port: Communication Loss Response This parameter specifies how the drive will respond to a network communication failure if the option port has been selected as the drive control source (P.000 = OP). Parameter Range: Network-dependent Default Setting: 0 Parameter Type: Tunable Refer also to parameters: P.000 Control Source For AutoMax applications, refer to the AutoMax Network Communication Option Board manual (D2-3308).
. P.064 Option Port: Network Trim Reference Source This parameter specifies where the drive gets its trim reference when the option port is selected as the control source (P.000 = OP). Parameter Range: Option board-dependent. See option board instruction manual. Default Setting: 0 Parameter Type: Configurable Refer also to parameters: P.063 Option Port: Network Reference Source U.
P.066 to P.069 Network Output Register 1 Source through Network Output Register 4 Source These parameters select the signal written to the option port network output registers 1 through 4. Parameter Range: 0 = (P.066) Motor Kw display value (P.067) Motor torque display value* (P.068) Output power factor (P.069) Encoder counter (x4)* 1 = Speed reference rate limit output* See figure 4.9.
P.066 to P.069 Network Output Register 1 Source through Network Output Register 4 Source (continued) P.066 0 = Motor KW display value . . . 12 P.067 0 = Motor torque display value . . . 12 Network Module Network Output Register 1 P.068 Network Output Register 2 0 = Output power factor . . . 12 Network Output Register 3 Network Output Register 4 P.069 0 = Encoder counter (x 4) . . . 12 Figure 4.
. P.090 Diagnostics Source This parameter is used to select internal information such as I/O data, network statistics, etc., for display in parameter P.091.
P.091 Diagnostics Display (continued) displayed as a four-digit combination of 1s and 0s (1 = on, 0 = off) in the following manner: Four-Character Display P.090 = 1, terminal strip digital inputs P.090 = 2, terminal strip digital inputs P.090 = 4, RMI digital inputs 4 8 4 3 7 3 2 6 2 1 5 1 P.095 Power Module Output Amps This parameter displays the maximum output current rating of the drive. The maximum value of Current Limit (P.005) corresponds to P.095.
P.099 Power Module Type This parameter displays the type of Power Module the drive is configured for. Parameter Range: N/A Default Setting: N/A Parameter Type: Read only Refer also to parameters: N/A The Power Module type is displayed in the format nnn.V where nnn represents the drive’s output current rating in amps divided by 10 and V represents the drive’s voltage rating (4 = 460 V). For example, the display 64.4 represents 643 amps, 460 V. 4.6.3 Second Menu V/Hz Parameter Descriptions (H.
H.001 Motor Nameplate Base Frequency (continued) The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and the setting of Torque Boost Voltage in H.003. See figure 4.10. 100% Maximum V/Hz Motor Voltage, H.000 (volts) Minimum V/Hz 30 Output Frequency (Hz) H.001 Figure 4.10 – Volts/Hz Ratio H.002 Motor Nameplate Amps This parameter is the motor amp rating as it appears on the motor nameplate.
H.003 Torque Boost Voltage This parameter sets the percentage of output voltage boost at zero frequency. It is set as a percentage of Motor Nameplate Volts (H.000). Parameter Range: 0.0% to 20.0% of nominal inverter voltage Default Setting: 0.5% Parameter Type: Configurable Refer also to parameters: H.000 Motor Nameplate Volts Important: If you set H.003 = 0, you must perform the identification test (using H.020) prior to running.
H.004 Slip Compensation This parameter is used to improve motor speed regulation by increasing the output frequency applied to the motor (the percentage of frequency rise at Power Module Output Amps (P.095)). Parameter Range: 0.0% to 10.0% of base frequency (H.001) Default Setting: 0.0% (no slip compensation) Parameter Type: Tunable Refer also to parameters: P.095 Power Module Output Amps H.
H.005 DC Braking Enable This parameter enables or disables DC braking. Parameter Range: ON = Enable DC braking OFF = Disable DC braking Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.025 Stop Type H.006 DC Braking Start Frequency H.007 DC Braking Current H.008 DC Braking Time H.017 Input Power/Snubber Configuration Important: This function will not provide holding torque as a mechanical brake. DC braking is only operative when Stop Type (P.025) is set to 1 (ramp stop).
H.007 DC Braking Current This parameter sets the DC current level applied to the motor during DC braking. Parameter Range: 0 to 100% of motor nameplate amps Default Setting: 10 Parameter Type: Tunable Refer also to parameters: H.005 DC Braking Enable H.006 DC Braking Start Frequency H.008 DC Braking Time With DC braking enabled (H.005 = ON), the braking torque by the motor is defined by a percentage of motor rated amps (100% of motor rated amps). Important: If H.
H.009 Avoidance Frequency Enable This parameter enables the avoidance frequency bands selected in H.011, H.013, and H.015. Parameter Range: OFF = Disable avoidance frequency processing ON = Enable avoidance frequency processing Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.003 Minimum Speed P.004 Maximum Speed H.010 to H.
H.010, H.012, H.014 Avoidance Frequency Midpoint 1, 2, and 3 This parameter specifies the midpoint of each avoidance frequency band selected in H.011, H.013, and H.015. Parameter Range: 0.0 to 200.0 Hz Default Setting: 0.0 Parameter Type: Tunable Refer also to parameters: H.009 Avoidance Frequency Enable H.011, H.013, H.015 Avoidance Frequency Band 1, 2, and 3 The adjusted values may be in any order.
H.016 Sync Direction When starting into a rotating load is required, this parameter selects the direction in which the drive will search in order to synchronize to motor speed.
H.017 Input Power/Snubber Configuration (continued) ! ATTENTION: When connected to a non-regenerative common DC bus, regeneration may cause a rise in DC bus voltage. Be aware that other drives on the bus may experience an unexpected speed increase due to the high bus voltage. Failure to observe this precaution may result in bodily injury. Set H.017 = 0 for LiquiFlo applications. For AC input Power Modules (200-230 V, 3-phase, 50/60 Hz or 380-460 V, 3-phase, 50/60 Hz), set H.017 = 0 or 1.
. H.018 Volts/Hertz Curve Type This parameter provides an application-dependent selection of nominal motor voltage versus frequency. This selection is effective from any control source. Parameter Range: 0 = Linear V/Hz curve 1 = Optimized V/Hz curve 2 = Squared V/Hz curve Default Setting: 0 Parameter Type: Configurable Refer also to parameters: H.003 Torque Boost Voltage Set H.018 = 0 for constant torque applications (such as extruders and conveyors). Set H.
H.019 Identification Result This parameter displays the result of the identification procedure. Normally, the identification procedure will be successful, and the value in H.019 will be = 0. Parameter Range: 0 = Identification procedure successful. No fault. 1 = A logged error aborted the identification procedure. Refer to section 5.3 for how to determine the cause of the fault. Remove the cause and repeat the procedure. 2 = A function loss aborted the identification procedure.
H.020 Identification Request (continued) ! ATTENTION: The motor shaft can rotate in either direction by up to one (1) revolution, providing minimum torque immediately after the identification procedure has been started. Stay clear of rotating machinery. Failure to observe this precaution could result in bodily injury. ATTENTION: Carrier Frequency (P.047) and Current Limit (P.005) must be set correctly before activating the identification procedure to avoid motor overloading and/or overheating.
H.021 AC Line Volts This parameter is the phase-to-phase line voltage provided to the drive input power terminals. Parameter Range: 300 to 565 VAC Default Setting: 460 Parameter Type: Configurable Refer also to parameters: N/A The value entered should be within 10% of actual line voltage. If this parameter is set too low, it may cause a drive fault on overvoltage. H.022 Overfrequency Limit This parameter provides overspeed protection by setting the fault level for maximum frequency output.
4.6.4 Second Menu Vector Parameter Descriptions (U.000 to U.048) U.000 Torque Reference Source This parameter specifies the source for the torque reference when torque regulation is selected. Parameter Range: 0 = Speed loop output 1 = Terminal strip analog input 2 = Option port (network torque reference register)* 3 = Selected speed reference * Default Setting: 0 Parameter Type: Configurable Refer also to parameters: P.
U.001 Encoder PPR This parameter selects the number of pulses per revolution (PPR) of the encoder being used or selects sensorless vector control (SVC) if no encoder is used. If SE is not selected, the value of this parameter is automatically set when self-tuning (U.008) is successful. Parameter Range: 512 = 512 PPR 1024 = 1024 PPR 2048 = 2048 PPR 4096 = 4096 PPR SE = No encoder connected. Operate in sensorless vector control (SVC).
U.002 Motor Poles This parameter identifies the number of poles in the motor. This parameter must be entered before parameter U.005 (Motor Nameplate RPM). Parameter U.005 is limited by the number of motor poles entered into parameter U.002. Parameter Range: 2 = 2 poles 4 = 4 poles 6 = 6 poles 8 = 8 poles Default Setting: 4 Parameter Type: Configurable Refer also to parameters: U.003 Motor Nameplate Base Frequency U.005 Motor Nameplate RPM ! ATTENTION: The setting of parameters U.
1 U.003 Motor Nameplate Base Frequency This parameter identifies the motor base frequency as it appears on the motor nameplate. This parameter must be entered before parameter U.005 (Motor Nameplate RPM). Parameter U.005 is limited by the motor base frequency. Parameter Range: 15.0 to 240.0 Hz Default Setting: 60.0 Parameter Type: Configurable Refer also to parameters: U.002 Motor Poles U.005 Motor Nameplate RPM ! ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002 (Motor Poles), U.
U.005 Motor Nameplate RPM This parameter identifies the motor rated RPM as it appears on the motor nameplate. This parameter must be set prior to activating the torque control self-tuning procedure (U.008). Parameter Range: * Default Setting: Power Module-dependent, see Appendix C Parameter Type: Configurable Refer also to parameters: U.002 Motor Poles U.003 Motor Nameplate Base Frequency U.008 Torque Self-Tune Enable *The actual adjustment range changes based on the values in U.
U.006 Magnetizing Current This parameter identifies the percentage of magnetizing current (no load amps) with respect to motor rated amps. Parameter Range: 10.0 to 80.0% Default Setting: Power Module-dependent, see Appendix C Parameter Type: Configurable Refer also to parameters: U.008 Torque Self-Tune Enable A value is automatically generated for this parameter when self-tuning is performed (U.008).
U.008 Torque Self-Tune Enable This parameter enables the self-tuning procedure. Parameter Range: ON = Enable self-tuning OFF = Disable self-tuning Default Setting: OFF Parameter Type: Configurable Refer also to parameters: U.001 Encoder PPR (FVC only) U.006 Magnetizing Current ! ATTENTION: The motor must be uncoupled from the drive load during self-tuning operation or incorrect parameter values will result. This includes any shaft-coupled devices such as reducers, belts, or brakes.
. U.009 Torque Self-Tune Result This parameter displays the results of the self-tuning operation requested by parameter U.008. Parameter Range: 0 = Self-tuning successful 1 = User initiated a normal stop. Self-tuning aborted. 2 = Emergency stop or fault stop occurred during self-tuning. Self-tuning aborted. 3 = Motor or encoder direction in reverse. Motor must rotate in a clockwise direction facing the motor/tach end. The encoder leads might also be reversed if the motor direction is correct.
U.013 Speed Regulator Integral Gain This parameter selects the lead frequency of the PI amplifier in the speed loop. This value affects the dynamic performance of the speed regulation of the motor. Parameter Range: 0.02 to 327.67 radians/second Default Setting: Power Module-dependent, see Appendix C Parameter Type: Tunable Refer also to parameters: N/A For most applications, it is recommended that this parameter not be adjusted.
U.015 Torque Regulator Integral Gain This parameter determines the performance of the torque regulator. Parameter Range: 10.0 to 628.0 radians/second Default Setting: Power Module-dependent, see Appendix C Parameter Type: Tunable For most applications, it is recommended that this value not be changed. Refer also to parameters: U.014 Torque Regulator Proportional Gain The higher the gain, the higher the performance of the torque loop.
U.017 Motor Top Speed This parameter selects the top speed that the motor can reach. Parameter Range: U.005 to 7200 RPM* Default Setting: Power Module-dependent, see Appendix C Parameter Type: Configurable Refer also to parameters: P.004 Maximum Speed P.005 Current Limit U.002 Motor Poles U.005 Motor Nameplate RPM *To determine the upper limit of U.017, the drive compares the results of two formulas and uses the lower value: For FVC operation (U.001 ≠ SE): 4 x sync speed or 240 x 120 U.
U.019 Flux Current Regulator Proportional Gain This parameter determines the performance of the magnetizing current regulator. For most applications, it is recommended that this parameter not be changed. Parameter Range: 0.10 to 31.99 Default Setting: Power Module-dependent, see Appendix C Parameter Type: Tunable Refer also to parameters: U.020 Flux Current Regulator Integral Gain U.
U.022 Motor Nameplate Horsepower This parameter identifies the motor horsepower as it appears on the motor nameplate. Parameter Range: 0.3 to 2000.0 HP Default Setting: Power Module-dependent, see Appendix C Parameter Type: Configurable Refer also to parameters: U.002 Motor Poles U.003 Motor Nameplate Base Frequency U.004 Motor Nameplate Amps U.005 Motor Nameplate RPM U.006 Magnetizing Current U.007 Motor Nameplate Volts U.
U.024 High DC Bus Fault Avoidance Enable This parameter selects how the drive responds to high bus voltage. Parameter Range: OFF = Drive will not attempt to regulate the DC bus on a high bus condition This feature is not available if the drive is configured as a torque regulator. Default Setting: OFF Parameter Type: Tunable Refer also to parameters: P.002 Decel Time 1 P.
U.026 Current Compounding Gain This parameter specifies the gain applied to the speed PI output. This is used to generate the current compounding signal that is subtracted from the speed loop reference. Parameter Range: 0.0 to 1.000 Default Setting: 0.0 (Current compounding disabled) Parameter Type: Tunable Refer also to parameters: U.027 Inertia Compensation Gain U.028 Losses Compensation Gain Refer to the speed loop block diagram in Appendix G. U.
U.028 Losses Compensation Gain This parameter specifies the gain applied to the speed loop reference signal to generate the losses compensation signal. The result is added to the speed PI output to produce the torque reference signal. Parameter Range: 0.0 to 1.000 Default Setting: 0.0 (Disable losses compensation) Parameter Type: Tunable Refer also to parameters: U.026 Current Compounding Gain U.
U.031 SVC Sync Direction When starting into a rotating load is required, this parameter selects the direction in which the drive will search in order to synchronize to motor speed.
U.040 Outer Control Loop Feedback Source This parameter specifies what is used as the outer loop feedback signal. Parameter Range: 0 = Terminal strip analog input scaled (see Appendix F) 1 = Speed loop PI output (torque reference, 4095 = 150% torque) Default Setting: 0 Parameter Type: Configurable Refer also to parameters: U.041 Outer Control Loop Lead/Lag Select U.042 Outer Control Loop Lead/Lag Low Frequency U.043 Outer Control Loop Lead/Lag Ratio U.044 Outer Control Loop Reference Gain U.
U.042 Outer Control Loop Lead/Lag Low Frequency This parameter specifies the lead/lag low break frequency of the outer control loop feedback. Parameter Range: 0.01 to 34.90 radians/second Default Setting: 1.0 Parameter Type: Tunable Refer also to parameters: U.040 Outer Control Loop Feedback Source U.041 Outer Control Loop Lead/Lag Select U.043 Outer Control Loop Lead/Lag Ratio U.044 Outer Control Loop Reference Gain U.045 Outer Control Loop Proportional Gain U.
U.044 Outer Control Loop Reference Gain This parameter specifies the gain to be applied to the reference entering the outer control loop. Parameter Range: -5.000 to +5.000 Default Setting: 1.000 Parameter Type: Tunable Refer also to parameters: U.040 Outer Control Loop Feedback Source U.041 Outer Control Loop Lead/Lag Select U.042 Outer Control Loop Lead/Lag Low Frequency U.043 Outer Control Loop Lead/Lag Ratio U.045 Outer Control Loop Proportional Gain U.046 Outer Control Loop Integral Gain U.
U.046 Outer Control Loop Integral Gain This parameter selects the integral gain of the outer control loop PI amplifier. Parameter Range: 0.01 to 141.37 radians/sec Default Setting: 2.00 Parameter Type: Tunable Refer also to parameters: U.040 Outer Control Loop Feedback Source U.041 Outer Control Loop Lead/Lag Select U.042 Outer Control Loop Lead/Lag Low Frequency U.043 Outer Control Loop Lead/Lag Ratio U.044 Outer Control Loop Reference Gain U.045 Outer Control Loop Proportional Gain U.
. U.048 Outer Control Loop Proportional Trim Enable This parameter enables the gain block on the output of the outer control loop PI block. Parameter Range: OFF = Disable proportional trim ON = Enable proportional trim Default Setting: OFF Parameter Type: Configurable Refer also to parameters: U.040 Outer Control Loop Feedback Source U.041 Outer Control Loop Lead/Lag Select U.042 Outer Control Loop Lead/Lag Low Frequency U.043 Outer Control Loop Lead/Lag Ratio U.
4-90 LiquiFlo AC Drive, Software Reference Version 6.
CHAPTER 5 Troubleshooting the Drive Using Error Codes The drive can display two kinds of error codes, called alarm and fault codes, to signal a problem detected during self tuning or drive operation. Fault and alarm codes are shown in tables 5.1 and 5.2. A special type of fault code, which occurs rarely, is the fatal fault code. If the code you see is not in tables 5.1 or 5.2, refer to section 5.4. Alarm Codes An alarm condition is signified by a two- or three-letter code flashing on the display.
5.1 Identifying Alarm Codes and Recovering LiquiFlo drive alarm codes are shown in table 5.1. Note that the alarm code will only be displayed for as long as the problem exists. Once the problem has been corrected, the alarm code will disappear from the display. Table 5.1 – List of Alarm Codes Code HIdc Alarm Description High DC bus voltage Alarm Cause The DC bus is charged above the trip threshold. (If U.018 > 415, DC bus is above 741 VDC. If U.018 ≤ 415, DC bus is above 669 VDC.
5.2 Identifying Fault Codes and Recovering ! ATTENTION: DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life. LiquiFlo drive fault codes are shown in table 5.2.
Table 5.2 – List of Fault Codes (Continued) Code IPL LU Fault Description Input phase loss Low DC bus voltage Fault Cause Voltage ripple on DC bus due to missing input phase or an imbalance between phases. DC bus voltage too low. Line dip too long (P.042). Input rectifier diodes defective. nCL Network comm loss Communications with the AutoMax network have been lost. nId Identification Request not yet performed (V/Hz only) Overcurrent (steady state). Trips at 190% to 200% rated current.
Table 5.2 – List of Fault Codes (Continued) Code OF OH OL OPL OSP PUc PUn PUo SF SrL Fault Description Overfrequency Fault Cause Drive has exceeded maximum allowable output frequency. Regenerating energy is too high. Stability or slip compensation circuit adds frequency reference. If H.016 ON, searching current is too high. Motor is too small. Corrective Action Vector: Check parameters Encoder PPR (U.001), Motor Poles (U.002), Base Frequency (U.003).
Table 5.2 – List of Fault Codes (Continued) Code UAr UbS Fault Description Spurious host PC comm interrupt Asymmetrical bus fault. Look at the 3 LEDs on the Power Module Interface board. They indicate which fault has occurred by flashing in unison. 1 = Input Ground Fault; 2 = Asymmetrical Bus; 3 = Slow Ramp Rate of DC Bus 5.3 Fault Cause Regulator board failure. Corrective Action Replace Regulator board. One of 3 different faults has ocurred: 1.
Step 2. Press the ▼ key until Err is displayed. E SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START ENTER RELIANCE ELECTRIC Step 3. Press the ENTER key. osp SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START If no faults have occured, Err will be displayed again.
Step 6. Press the ▼ key. 22.i7 SPEED VOLTS AMPS Hz Kw TORQUE Password STOP RESET RUNNING AUTO MAN Forward Reverse PROGRAM RUN JOG REMOTE JOG AUTO FORWARD REVERSE PROGRAM START The display shows the time stamp, which is based on a 24-hour clock. Use the arrow keys to move between the day and time data. ENTER RELIANCE ELECTRIC Step 7. Press the PROGRAM key, which displays the error log entries again.The display shows the error log entry viewed prior to or associated with the time stamp. Step 8.
5.4 Identifying Fatal Fault Codes and Recovering Fatal fault codes are distinguished by the letter F preceding the code. They normally indicate a malfunction of the microprocessor on the Regulator board. In some cases, fatal fault codes can be reset and the drive can be re-started. Table 5.3 lists the fatal fault codes which can be reset. If any other fault code appears on the display, you will need to replace the Regulator board.
5-10 LiquiFlo AC Drive, Software Reference Version 6.
APPENDIX A Alphabetical Listing of Parameters First Menu General Parameters Accel Time 1 (RAMP 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P.001 Control Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P.000 Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P.005 Decel Time (RAMP 1). . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-2 Second Menu General Parameters (continued) Output Relay Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Module Output Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Module Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preset Speed 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preset Speed 2 . . . .
Second Menu Vector Parameters AC Line Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .U.018 Current Compounding Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .U.026 Encoder PPR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .U.001 Field Weakening Start RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .U.
Second Menu RMI Parameters (continued) Digital Output 1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Output 1 Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Output 2 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Output 2 Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Output 3 Configuration . . . .
APPENDIX B Record of User Parameter Settings Parameter No. P.000 First Menu P.001 General P.002 P.003 P.004 P.005 P.006 Parameter Name Control Source Accel Time 1 (RAMP 1) Decel Time 1 (RAMP 1) Minimum Speed Maximum Speed Current Limit Second Menu Password Second P.007 Menu P.008 General P.009 P.010 P.011 P.012 P.013 P.014 P.015 P.016 P.017 P.018 P.019 P.020 P.021 P.022 P.023 P.024 P.025 P.026 P.027 P.028 P.029 P.030 P.031 P.032 P.033 P.034 P.035 P.036 P.037 P.038 P.
Parameter No. Second P.040 Menu P.041 General P.042 (cont’d) P.043 P.044 P.045 P.047 P.048 P.049 P.050 P.051 P.052 P.053 P.054 P.055 P.060 P.061 P.062 P.063 P.064 P.065 P.066 P.067 P.068 P.069 P.090 P.091 P.095 P.097 P.098 P.
Parameter No. Second H.000 Menu H.001 Volts/ H.002 Hertz H.003 H.004 H.005 H.006 H.007 H.008 H.009 H.010 H.011 H.012 H.013 H.014 H.015 H.016 H.017 H.018 H.019 H.020 H.021 H.
Parameter No. Second U.000 Menu U.001 Vector U.002 U.003 U.004 U.005 U.006 U.007 U.008 U.009 U.012 U.013 U.014 U.015 U.016 U.017 U.018 U.019 U.020 U.021 U.022 U.023 U.024 U.025 U.026 U.027 U.028 U.030 U.031 U.032 U.040 U.041 U.042 U.043 U.044 U.045 U.046 U.047 U.
Parameter No. Second r.001 Menu r.002 RMI r.003 r.004 r.005 r.006 r.007 r.008 r.009 r.010 r.011 r.014 r.015 r.016 r.020 r.021 r.022 r.025 r.030 r.031 r.032 r.033 r.034 r.035 r.036 r.037 r.040 r.041 r.042 r.043 r.044 r.045 r.046 r.050 r.051 r.052 r.053 r.056 r.057 r.058 r.059 r.060 r.063 r.064 r.065 r.
B-6 LiquiFlo AC Drive, Software Reference Version 6.
APPENDIX C Power Module-Dependent Parameter Default Values Second Menu General Parameters (USA Defaults) B-Frame Parameter Number P.047 Parameter Name Carrier Frequency (kHz) C-Frame D-Frame 41L4060 41LR4060 50LW4060 50LR4060 64LW4060 64LR4060 120L4060 2 2 2 2 Second Menu Volts/Hertz Parameters (USA Defaults) B-Frame Parameter Number H.002 Parameter Name Motor Nameplate Amps C-Frame D-Frame 41L4060 41LR4060 50LW4060 50LR4060 64LW4060 64LR4060 120L4060 386.0 500.0 643.0 1157.
C-2 LiquiFlo AC Drive, Software Reference Version 6.
APPENDIX D Default Parameter Settings First and Second Menu General Parameters Parameter No. Parameter Name USA (P.049=USA) EUROPE (P.049=EUr) JAPAN (P.049=JPn) P.000 Control Source LOCL LOCL LOCL P.001 Accel Time 1 20.0 20.0 20.0 P.002 Decel Time 1 20.0 20.0 20.0 P.003 Minimum Speed P.048 = U-H P.048 = UEC 5.0 Hz 150 RPM 5.0 Hz 150 RPM 5.0 Hz 150 RPM P.004 Maximum Speed P.048 = U-H P.048 = UEC 60.0 Hz 1722 RPM 50.0 Hz 1400 RPM 52.7 Hz 1500 RPM P.
Second Menu General Parameters (Continued) Parameter No. Parameter Name USA (P.049=USA) EUROPE (P.049=EUr) JAPAN (P.049=JPn) ** U.017 ** U.017 ** U.017 Read Only 0 0 OFF OFF OFF P.028 Speed Display Scaling P.048 = U-H P.048 = UEC P.029 Elapsed Time Meter P.030 Elapsed Time Meter Reset P.031 Preset Speed 1 P.048 = U-H P.048 = UEC 5.0 Hz 150 RPM 5.0 Hz 150 RPM 5.0 Hz 150 RPM P.032 Preset Speed 2 P.048 = U-H P.048 = UEC 5.0 Hz 150 RPM 5.0 Hz 150 RPM 5.0 Hz 150 RPM P.
Second Menu General Parameters (Continued) Parameter No. Parameter Name USA (P.049=USA) EUROPE (P.049=EUr) JAPAN (P.049=JPn) 0 0 0 Read Only Read Only Read Only P.064 Option Port: Network Trim Ref. Source P.065 Option Port: Type and Version P.066 Network Output Register 1 Source 0 0 0 P.067 Network Output Register 2 Source 0 0 0 P.068 Network Output Register 3 Source 0 0 0 P.069 Network Output Register 3 Source 0 0 0 P.090 Diagnostics Source 0 0 0 P.
Second Menu Vector Parameters Parameter No. Parameter Name USA (P.049=USA) EUROPE (P.049=EUr) JAPAN (P.049=JPn) 0 0 0 1024 2048 1024 4 4 4 60.0 50.0 60.0 * U.000 Torque Reference Source U.001 Encoder PPR U.002 Motor Poles U.003 Motor Nameplate Base Frequency U.004 Motor Nameplate Amps * * U.005 Motor Nameplate RPM * * * U.006 Magnetizing Current * * * U.007 Motor Nameplate Volts 460 380 460 U.008 Torque Self-Tune Enable OFF OFF OFF U.
APPENDIX E Configuring the Digital Inputs When the RMI Board Is Installed in the Drive The LiquiFlo Regulator board contains three user-configurable digital inputs. Parameters P.007 (Terminal Strip Digital Inputs Configure) and P.008 (Terminal Strip Speed Reference Source) are used to specify how these digital inputs are used. If an optional Remote Meter Interface (RMI) board is installed in the drive, four additional digital inputs are available. RMI parameter r.
Summary of Options for P.007, P.008, and r.030 0= 1= 2= 3= 4= 5= 6= 7= 8= 9= 10 = 11 = 12 = P.
Example 1 Functions to be assigned to the Regulator board terminal strip: • 2 preset speeds • TRQ/SPD • FWD/REV Function to be assigned to RMI terminal strip: • MOP To configure the Regulator board digital inputs for the above functions, P.007 should be set to 10, and P.008 should be set to 2. Using the Option Comparison Tables, a setting of 10 in P.007 allows P.008 to be set to 2. To configure the RMI terminal strip for the MOP function, r.030 should be set to 2.
E-4 LiquiFlo AC Drive, Software Reference Version 6.
APPENDIX F Using the Terminal Strip Analog Input An analog reference input is provided at terminals 12 through 15 on the drive’s Regulator board. This input accepts either a +/-10 VDC or 0 to 20 mA signal. The analog-to-digital conversion provides 10-bit plus sign resolution and a digital range of +/-1023. The analog input can be used as a reference for: • Speed reference (P.000, P.007/P.008) • Trim reference (P.014) • Torque reference (vector control only) (U.000) • Outer control loop feedback (U.
F.1 Configuring the Analog Input Parameter P.011 is used to specify the type of input and whether it is to be inverted after it is converted by the drive. The parameter setting should coincide with the position of jumper J4 on the Regulator board. For example, if a voltage input is applied, J4 should be set to +/- 10 VDC and P.011 should be between 0 and 3. If a current input is applied, J4 should be set to 0 to 20 mA and P.011 should be between 4 and 7. If P.
Figure F.2 illustrates how the analog signal is scaled internally by the drive when it is used as the speed or trim reference. The solid line indicates the conversion when the non-inverted state is selected (P.011 is even). The dashed line indicates the conversion when the inverted state is selected (P.011 is odd). +Max Spd (P.004) +Min Spd (P.003) -10 vdc -Min Spd (P.003) +10 vdc +20 ma -Max Spd (P.004) Terminal Strip Analog Input P.011 is even = non-inverted P.011 is odd = inverted Figure F.
To adjust the offset (P.009): Step 1. Verify that the analog input is configured as the speed reference control source (P.000 = rE or LOCL and AUTO is selected), P.008 = 0, and U.000 = 0). Step 2. Display the converted value of the analog input using the selected speed reference display mode. (Refer to chapter 3 for the procedure for displaying the selected speed reference.) Step 3. Adjust P.
• The maximum negative analog input value (-10VDC) corresponds to the negative torque limit of the drive (-150% of the rated motor torque). • The minimum analog input value (0 VDC or 0 mA) corresponds to zero torque reference. Refer to the LiquiFlo drive hardware reference manual for terminal location, wiring guidelines, and jumper settings. F.
On state Off state Stop threshold Default = 0.20 VDC Start threshold Default = 0.33 VDC Analog Input (0 - 10 VDC) Figure F.3 – Hysteresis Band Created by the Start and Stop Thresholds (Default Configuration) Important: The terminal strip start input then becomes another stop function and start permissive condition: • When the start input is open, the drive will stop and remain stopped. • The start input must be closed to allow the drive to start. The control source must be the terminal strip (P.
F.4.1.2 Start Threshold Range The default value of the start threshold is 33 A/D counts, which corresponds to 0.33 VDC (nominal). The start threshold minimum value is 0 counts. The start threshold maximum value is 2000 counts. F.4.2 Using the Level Sense Start Enable Feature and the Analog Input Start/Stop Feature The level sense start enable feature, configured with parameter P.054 (Level Sense Start Enable), can be used with the analog input start/stop feature.
F-8 LiquiFlo AC Drive, Software Reference Version 6.
APPENDIX G Drive Regulation Overview The LiquiFlo digital drive provides vector or volts/hertz regulation of AC motors. Parameter P.048 (Volts/Hertz or Vector Regulation) is used to select the type of regulation for the application. Volts/Hertz Regulation (P.048 = U-H) Volts/hertz regulation provides general-purpose open-loop AC drive control. It does not use an encoder feedback device.
If a Remote Meter Interface (RMI) board is installed, P.064 is used to select the OCL reference as follows for FVC/SVC applications only: • 0 = RMI analog input • 1 to 8 = Preset speed 1 to 8 (P.031 to P.038), respectively If no option board is installed, P.064 is used to select the OCL reference for FVC/SVC applications only: • 0 = Preset speed 8 (P.038) • 1 to 8 = Preset speed 1 to 8 (P.031 to P.
Figure G.1 – Volts/Hertz Regulator Block Diagram Drive Regulation Overview G-3 Option Serial Remote Local Speed Ref. Selection P.000 H.004 P.020 P.015 P.014 P.016 Slip Comp Jog Ref Trim Ref Speed Ref Draw Gain + + Ride Thru Search Mot. Freq. DC Bus Voltage Overload Avoid Freq. Current Fbk + H.009 to H.
AC Line Reference Selection See figure G.4 Speed Loop See figure G.5 Torque Controller Speed feedback Power Devices Current feedback dx/dt Motor Relative shaft position E Figure G.2 – Flux Vector Control Block Diagram AC Line Reference Selection See figure G.4 Speed Loop See figure G.5 Estimated speed feedback Torque Controller Power Devices Current feedback Motor Figure G.3 – Sensorless Vector Control Block Diagram G-4 LiquiFlo AC Drive, Software Reference Version 6.
Figure G.4 – Reference Detail Drawing of the Vector Regulator Drive Regulation Overview G-5 3 2 1 Preset Speeds MOP Direct 1 P.063 Manual Setpoint 0 1 2 3 2 4 Broadcast 5 6 7 8 0 1 2 3 4 5 6 7 If AutoMax option, then drop 1, register 34 If ControlNet option, then third word of scheduled data If RMI option, then RMI analog input (U.017 @ 10V) AutoMax option only 3 0 1 2 3 4 5 6 7 8 P.
Figure G.5 – Speed Loop Detail Drawing of the Vector Regulator G-6 LiquiFlo AC Drive, Software Reference Version 6.4 Speed Ref 0 2 1 1 0 + +/- U.017 x U.027 x U.028 Current compounding - + 2 Network Inertia comp enable Rate output * (To Outer Control Loop) If AutoMax option, then drop 1, register 53, bit 1 If ControlNet option, then N10:30 bit 1 * * + + + (To Outer Control Loop) Iq Fdbk * Torque Controller U.014 U.015 U.019 U.020 U.
Figure G.6 – Vector Speed PI and Iq Reference Limit Selection Drive Regulation Overview G-7 Current Limit (P.005) Iq ref low limit Netw speed PI limit enable (drop 1, reg 53, bit 2) P.000 = OP Netw com active Netw Speed PI low limit (drop 1, reg 60) Netw Speed PI high limit (drop 1, reg 59) Magnetizing Current (U.006) f(P.005, U.006) Iq ref high limit f(r.
Figure G.7 – Outer Control Loop Block Diagram G-8 LiquiFlo AC Drive, Software Reference Version 6.4 8 P.038 Network - See network specific I/M for details. RMI None Option Board Installed + OCL * feedback x U.044 Available in network read registers 8 Broadcast 8 * 0 1 Direct Broadcast 1 P.064 0 1 P.064 8 0 1 RMI Analog Input P.031 P.038 P.038 P.031 P.064 0 * 100 x U.047 Input 20 msec scan period OCL L/L Low Freq (U.042) Lead/ Lag Init OCL L/L Ratio (U.
INDEX A AC Line Volts (H.021), 4-67 AC Line Volts (U.018), 4-78 Accel Time 1 (RAMP 1) (P.001), 4-7 to 4-8 Accel Time 2 (RAMP 2) (P.017), 4-24 Alarm codes, 5-1, 5-2 Analog input, see Input, Analog Analog output, see Output, Analog AUTO/MAN Key Disable (P.052), 4-41 AutoMax Network Communication Option board, 4-7, 4-47, 4-48, 4-49, 4-51 Avoidance Frequency Band 1 (H.011), 4-61 Avoidance Frequency Band 2 (H.013), 4-61 Avoidance Frequency Band 3 (H.015), 4-61 Avoidance Frequency Enable (H.
H M H parameters, 4-54 to 4-67 listed alphabetically, A-2 High DC Bus Fault Avoidance Enable (U.024), 4-81 Magnetizing Current (U.006), 4-72 to 4-73 Manual Reference Preset Enable (P.053), 4-42 Maximum Speed (P.004), 4-9 Minimum Speed (P.003), 4-9 Monitor mode, 3-2 to 3-3 MOP Accel/Decel Time (P.023), 4-27 MOP Reset Configuration (P.024), 4-28 Motor Nameplate Amps (H.002), 4-55 Motor Nameplate Amps (U.004), 4-71 Motor Nameplate Base Frequency (H.001), 4-54 to 4-55 Motor Nameplate Base Frequency (U.
O OCL see Outer Control Loop OIM, see Operator Interface Module Open-loop regulation, see Volts/Hertz Regulation Operator Interface Module, 4-6 to 4-7, 4-15, 4-41, 4-44, 4-46 Option Port: Communication Loss Response (P.062), 4-48 Option Port: Network Reference Source (P.063), 4-48 Option Port: Network Trim Reference Source (P.064), 4-49 Option Port: Type and Version (P.065), 4-49 Outer Control Loop Feedback Source (U.040), 4-85 Outer Control Loop Integral Gain (U.
Snubber Resistor Kit, see Input Power/Snubber Configuration (H.017) Software Version Number (P.098), 4-53 Speed Display Scaling (P.028), 4-30 to 4-31 Speed loop, G-1, G-6 Speed reference, 4-6 to 4-7 displaying, 3-2 to 3-3 manual, 3-5 see also Minimum Speed (P.003) Maximum Speed (P.004) Terminal Strip Speed Reference Source (P.008) Draw Gain Percentage (P.016) Jog Speed Reference (P.
U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives Publication D2-3410-7 - June 2002 Copyright © 2002 Rockwell Automation, Inc. All Rights Reserved.